550.13-TG2Y (1001)
Unitary Products Group 13
TABLE 15: ELECTRICAL DATA
MODELS
LEU
MOTOR NAMEPLATE DATA MAX. WIRE
LENGTH
1
(
FT
.)
MAX. FUSE
SIZE
2
(A
MPS
)
MIN. DISC.
SWITCH SIZE
(A
MPS
)
POWER SUPPLY
HP
3
FLA
360
208-3-60
5 13.6 135 25 30
7-1/2 21.0 135 35 60
10 25.0 175 40 60
230/460-3-60
@230V
5 13.4 150 25 30
7-1/2 21.0 150 35 60
10 25.0 195 40 60
@460V
5 6.7 385 12 30
7-1/2 10.5 245 20 30
10 12.5 320 20 30
480
208-3-60
7-1/2 21.0 135 35 60
10 25.0 175 40 60
230/460-3-60
@230V
7-1/2 21.0 150 35 60
10 25.0 195 40 60
@460V
7-1/2 10.5 245 20 30
10 12.5 320 20 30
600
200-3-60
10 34.4 190 60 60
15 46.0 215 70 100
230/460-3-60
@230V
10 28.6 170 50 60
15 42.0 180 70 100
@460V
10 14.3 285 25 30
15 21.0 300 35 60
1.
Based on an 80% power factor and on a 3% voltage drop.
2.
Dual element, time delay fuses.
3.
For additional motor data, refer to blower motor and drive table.