Johnson Controls Ducted Systems 23
115°F 125°F
1000
77 33.8 3.0 - 20.8 13.1 - - - 28.9 3.4 - 20.4 11.8 - - -
72 32.3 3.0 - 23.8 18.0 12.3 - - 28.8 3.4 - 22.7 16.8 10.9 - -
67 30.8 3.0 - 26.7 23.0 17.2 11.5 - 28.4 3.4 - 24.9 21.8 15.9 10.0 -
62 30.4 3.0 - 29.1 27.9 22.2 16.5 10.8 28.0 3.4 - 27.4 26.8 20.8 14.8 8.9
1200
77 34.5 3.0 - 20.8 11.6 - - - 30.0 3.4 - 20.0 10.2 - - -
72 33.2 3.0 - 24.5 18.1 11.6 - - 29.7 3.4 - 23.0 16.6 10.1 - -
67 31.9 3.0 31.7 28.1 24.5 18.0 11.5 - 29.3 3.4 - 26.0 23.0 16.5 10.0 -
62 31.9 3.0 31.7 31.4 31.0 24.5 17.9 11.3 29.3 3.4 - 29.1 29.1 22.8 16.2 9.6
57 31.8 3.0 31.6 31.6 31.6 30.9 24.2 17.6 29.3 3.4 - 29.1 29.1 29.1 22.5 15.8
1400
77 35.2 3.0 31.7 20.9 10.0 - - - 31.1 3.3 30.6 19.5 8.5 - - -
72 34.0 3.0 32.3 25.2 18.1 11.0 - - 30.6 3.4 30.3 23.3 16.3 9.3 - -
67 33.1 3.0 32.9 29.5 26.1 18.9 11.6 - 30.3 3.4 30.1 27.1 24.1 17.0 9.9 -
62 33.3 3.0 33.0 33.0 33.0 26.7 19.3 11.8 30.6 3.4 30.2 30.2 30.2 24.8 17.6 10.4
57 33.6 3.0 33.1 33.1 33.1 33.1 27.0 19.3 30.9 3.4 30.3 30.3 30.3 30.3 25.2 17.9
1600
77 35.9 2.9 33.3 20.9 8.5 - - - 32.1 3.3 31.4 19.1 6.9 - - -
72 34.9 3.0 33.7 25.9 18.1 10.3 - - 31.5 3.3 31.2 23.7 16.1 8.5 - -
67 34.2 3.0 34.0 30.9 27.7 19.7 11.6 - 31.3 3.4 31.1 28.2 25.3 17.6 9.9 -
62 34.8 3.0 34.3 34.3 34.3 29.0 20.7 12.3 32.0 3.3 31.3 31.3 31.3 26.8 18.9 11.1
57 35.4 2.9 34.5 34.5 34.5 34.5 29.7 21.1 32.6 3.3 31.5 31.5 31.5 31.5 27.9 20.0
1800
72 35.7 2.9 35.0 26.6 18.1 9.7 - - 32.4 3.3 32.2 24.0 15.9 7.7 - -
67 35.4 2.9 35.2 32.3 29.3 20.5 11.6 - 32.3 3.3 32.1 29.3 26.5 18.2 9.9 -
62 36.3 2.9 35.6 35.6 35.6 31.3 22.1 12.8 33.3 3.3 32.4 32.4 32.4 28.7 20.3 11.9
57 37.2 2.9 35.9 35.9 35.9 35.9 32.5 22.8 34.2 3.3 32.7 32.7 32.7 32.7 30.7 22.1
2000
72 36.6 2.9 36.4 27.3 18.1 9.0 - - 33.3 3.3 - - - - - -
67 36.5 2.9 36.4 33.7 30.9 21.3 11.7 - 33.3 3.3 - - - - - -
62 37.8 2.9 36.9 36.9 36.9 33.6 23.5 13.3 34.6 3.3 - - - - - -
57 39.0 2.9 37.4 37.4 37.4 37.4 35.2 24.6 35.9 3.3 - - - - - -
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT049 Low Speed Compressor (4.0 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65