5.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
YM9FXC030BAA--FX + YM9FYC030BAA-A-X
5/8’’
16.0)
3/8’’
(Ф9.52)
5
10
25
40
YM9FXH030BAA--FX + YM9FYH030BAA-A-X
5/8’’
16.0)
3/8’’
(Ф9.52)
5
10
25
40
YM9FXC036BAA--FX+ YM9FYC036BAA-A-X
3/4’’
19.0)
3/8’’
(Ф9.52)
5
15
30
40
YM9FXH036BAA--FX+YM9FYH036BAA-A-X
3/4’’
19.0)
3/8’’
(Ф9.52)
5
15
30
40
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.