5168273-YIM-A-1115
18 Johnson Controls Unitary Products
XP180/240 - Standard Drive With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat
(Field Installed Accessory Only)
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
180
(15)
208-3-60 25 164 39 4.1 13.5 10
NONE - - - 88 110
E18 13.5 1 37.5 134.8 150
E36 27 2 74.9 134.8 150
E54 40.6 2 112.7 170.2 175
E72 54.1 2 150.2 181.6 200
230-3-60 25 164 39 3.9 13 10
NONE - - - 87.1 110
E18 18 1 43.3 141.2 150
E36 36 2 86.6 141.2 150
E54 54 2 129.9 158.7 175
E72 72 2 173.2 202 225
460-3-60 12.2 100 19 2.15 6.5 5
NONE - - - 43.3 50
E18 18 1 21.7 70.3 80
E36 36 2 43.3 70.3 80
E54 54 2 65 79.3 90
E72 72 2 86.6 101 110
575-3-60 9 78 14 1.6 5.2 4
NONE - - - 32.7 40
E18 18 1 17.3 54.3 60
E36 36 2 34.6 54.8 60
E54 54 2 52 63.5 70
E72 72 2 69.3 80.8 90
240
(20)
208-3-60 34.3 239 52 3.5 20 10
NONE - - - 121.2 150
E18 13.5 1 37.5 168 175
E36 27 2 74.9 168 175
E54 40.6 2 112.7 178.4 200
E72 54.1 2 150.2 214.9 225
230-3-60 34.3 239 52 3.5 19.4 10
NONE - - - 120.6 150
E18 18 1 43.3 174.7 175
E36 36 2 86.6 174.7 175
E54 54 2 129.9 174.7 175
E72 72 2 173.2 228.8 250
460-3-60 17.9 125 28 1.9 9.7 5
NONE - - - 62.6 80
E18 18 1 21.7 89.6 100
E36 36 2 43.3 89.6 100
E54 54 2 65 89.6 100
E72 72 2 86.6 116.7 125
575-3-60 12.8 80 20 1.5 7.8 4
NONE - - - 46.6 50
E18 18 1 17.3 68.3 70
E36 36 2 34.6 68.3 70
E54 54 2 52 68.3 70
E72 72 2 69.3 89.9 90