5168273-YIM-A-1115
Johnson Controls Unitary Products 19
XP180/240 - High Static Drive Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat
(Field Installed Accessory Only)
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
180
(15)
208-3-60 25 164 39 4.1 20 0
NONE - - - 84.5 100
E18 13.5 1 37.5 131.3 150
E36 27 2 74.9 131.3 150
E54 40.6 2 112.7 165.9 175
E72 54.1 2 150.2 178.1 200
230-3-60 25 164 39 3.9 19.4 0
NONE - - - 83.5 100
E18 18 1 43.3 137.6 150
E36 36 2 86.6 137.6 150
E54 54 2 129.9 154.2 175
E72 72 2 173.2 197.5 225
460-3-60 12.2 100 19 2.15 9.7 0
NONE - - - 41.5 50
E18 18 1 21.7 68.5 70
E36 36 2 43.3 68.5 70
E54 54 2 65 77.1 90
E72 72 2 86.6 98.7 110
575-3-60 9 78 14 1.6 7.8 0
NONE - - - 31.3 40
E18 18 1 17.3 52.9 60
E36 36 2 34.6 53.1 60
E54 54 2 52 61.7 70
E72 72 2 69.3 79 90
240
(20)
208-3-60 34.3 239 52 3.5 26 0
NONE - - - 117.2 150
E18 13.5 1 37.5 164 175
E36 27 2 74.9 164 175
E54 40.6 2 112.7 173.4 175
E72 54.1 2 150.2 210.9 225
230-3-60 34.3 239 52 3.5 25 0
NONE - - - 116.2 150
E18 18 1 43.3 170.3 175
E36 36 2 86.6 170.3 175
E54 54 2 129.9 170.3 175
E72 72 2 173.2 224.4 225
460-3-60 17.9 125 28 1.9 12.5 0
NONE - - - 60.4 70
E18 18 1 21.7 87.4 90
E36 36 2 43.3 87.4 90
E54 54 2 65 87.4 90
E72 72 2 86.6 114.5 125
575-3-60 12.8 80 20 1.5 10 0
NONE - - - 44.8 50
E18 18 1 17.3 66.5 70
E36 36 2 34.6 66.5 70
E54 54 2 52 66.5 70
E72 72 2 69.3 88.1 90