5168273-YIM-A-1115
20 Johnson Controls Unitary Products
XP180/240 - High Static Drive With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat
(Field Installed Accessory Only)
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
180
(15)
208-3-60 25 164 39 4.1 20 10
NONE - - - 94.5 110
E18 13.5 1 37.5 141.3 150
E36 27 2 74.9 141.3 150
E54 40.6 2 112.7 178.4 200
E72 54.1 2 150.2 188.1 200
230-3-60 25 164 39 3.9 19.4 10
NONE - - - 93.5 110
E18 18 1 43.3 147.6 150
E36 36 2 86.6 147.6 150
E54 54 2 129.9 166.7 175
E72 72 2 173.2 210 225
460-3-60 12.2 100 19 2.15 9.7 5
NONE - - - 46.5 50
E18 18 1 21.7 73.5 80
E36 36 2 43.3 73.5 80
E54 54 2 65 83.3 90
E72 72 2 86.6 105 110
575-3-60 9 78 14 1.6 7.8 4
NONE - - - 35.3 40
E18 18 1 17.3 56.9 60
E36 36 2 34.6 58.1 60
E54 54 2 52 66.7 70
E72 72 2 69.3 84 90
240
(20)
208-3-60 34.3 239 52 3.5 26 10
NONE - - - 127.2 150
E18 13.5 1 37.5 174 175
E36 27 2 74.9 174 175
E54 40.6 2 112.7 185.9 200
E72 54.1 2 150.2 220.9 225
230-3-60 34.3 239 52 3.5 25 10
NONE - - - 126.2 150
E18 18 1 43.3 180.3 200
E36 36 2 86.6 180.3 200
E54 54 2 129.9 180.3 200
E72 72 2 173.2 234.4 250
460-3-60 17.9 125 28 1.9 12.5 5
NONE - - - 65.4 80
E18 18 1 21.7 92.4 100
E36 36 2 43.3 92.4 100
E54 54 2 65 92.4 100
E72 72 2 86.6 119.5 125
575-3-60 12.8 80 20 1.5 10 4
NONE - - - 48.8 60
E18 18 1 17.3 70.5 80
E36 36 2 34.6 70.5 80
E54 54 2 52 70.5 80
E72 72 2 69.3 92.1 100