Installation Procedure Indoor Unit
INSTALLING THE INDOOR UNIT
Connection pipe requirement
Install the room air conditioner as follows
1. Remove the intake grill and side cover
(1) Remove the Air filters
(2) Remove the intake grilles
(3) Remove the Side cover (Right and left side)
2. Location of ceiling supension bolts
For half-concealed installation
Supension-bolt pitch should be as shown below
Ceiling Opening:Amm40mm 40mm
Ceiling panel
Ceiling Opening
640mm
Ceiling panel
15mm
Suspension bolt should
extend outward 30 to 50mm.
Suspension bolt pitch Amm
30mm
30mm
INDOOR UNIT (TOP VIEW)
Dimensions (Space Required for
installation)
10mm
155mm
300mm
Side cover A (Right side) Side cover A (Left side)
Intake grille
Air filter
Suspension bolt should
extend outward 30 to 50mm.
YIFFXC030BAEFA
YIFFXC036BAEFA
YIFFXC036BANFA
YIFFXC040BAEFB
YIFFXC040BANFA
Model
Diameter
Liquid side Gas side
Maximum length
Maximum height
(between indoor and outdoor)
9.52 mm 15.88mm 30 m 10m
19.05mm 30 m
9.52 mm 19.05mm 30 m
9.52 mm
9.52 mm 19.05mm 50 m
10m
15m
20m
YIFFYC030BAEFA
YIFFYC036BAEFA
YIFFYC036BANFA
YIFFYC040BAEFB
YIFFYC040BANFA
YIFFYC025BAEFA
Dimensions
A(mm)
Model
1248
1530
YIFFXC025BAEFA