EasyManua.ls Logo

York SPLIT-SYSTEM YHJF18 THRU 60 - Page 18

York SPLIT-SYSTEM YHJF18 THRU 60
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
510667-YTG-B-0509
18 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
LOW CFM
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
CONDENSING UNIT MODEL NO. YHJF60S41S1
INDOOR COIL MODEL NO. AHX60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 965 1165 1365
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 37.3 41.8 41.6 45.5 50.9 40.4 43.7 43.3 47.7 52.2 43.5 45.6 45.1 49.9 53.6
S.C. 35.2 32.0 27.8 27.8 23.7 38.1 35.1 30.0 30.0 24.9 41.1 38.2 32.2 32.3 26.1
KW 2.1 2.1 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.3 2.3 2.3 2.3 2.3
75
T.C. 36.2 39.9 39.8 43.6 48.4 39.0 41.6 41.3 45.5 49.8 41.8 43.3 42.8 47.4 51.2
S.C. 34.2 31.2 27.0 27.0 22.7 36.8 34.3 29.1 29.1 23.9 39.5 37.3 31.3 31.3 25.1
KW 2.4 2.4 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.6
85
T.C. 35.2 38.0 37.9 41.8 46.0 37.6 39.4 39.2 43.3 47.4 40.1 40.9 40.5 44.8 48.8
S.C. 33.2 30.5 26.1 26.1 21.7 35.5 33.5 28.3 28.3 22.9 37.8 36.5 30.4 30.4 24.0
KW 2.7 2.7 2.8 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.9 2.9 2.9 2.9 2.9
95
T.C. 34.1 36.0 36.0 39.9 43.6 36.2 37.3 37.1 41.1 45.0 38.3 38.5 38.2 42.3 46.5
S.C. 32.2 29.7 25.3 25.3 20.7 34.2 32.7 27.4 27.4 21.9 36.2 35.7 29.5 29.4 23.0
KW 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.2 3.2 3.2 3.2 3.2
105
T.C. 32.4 33.7 33.7 37.3 40.9 34.2 34.7 34.6 38.3 42.1 36.1 35.7 35.5 39.3 43.3
S.C. 30.6 28.8 24.3 24.3 19.6 32.3 31.1 26.4 26.3 20.8 34.1 33.3 28.5 28.4 22.0
KW 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.6 3.6 3.6 3.6 3.6
115
T.C. 30.6 31.4 31.4 34.7 38.3 32.3 32.1 32.1 35.5 39.2 33.9 32.8 32.8 36.3 40.1
S.C. 28.9 27.8 23.3 23.2 18.6 30.5 29.4 25.4 25.3 19.7 32.0 31.0 27.4 27.3 20.9
KW 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 4.0 4.0 4.0 4.0 4.0
125
T.C. 28.9 29.1 29.1 32.1 35.7 30.3 29.5 29.6 32.7 36.3 31.7 29.9 30.1 33.4 37.0
S.C. 27.3 26.9 22.4 22.2 17.5 28.6 27.8 24.4 24.2 18.7 30.0 28.6 26.4 26.3 19.9
KW 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
MV20D FC/MC62D 1.00 1.00 0.99
Furnace Coil T.C. S.C. KW
T*(8,L)X*C20 FC/MC62D 0.92 0.87 0.97
T*9X*C20 FC/MC62D 1.01 1.02 1.02
T*9X*D20 FC/MC62D 1.02 1.03 1.01
Y*(8,L)C*C20 FC/MC62D 0.97 0.94 0.99
(Y*9C/T*9V)*C20 FC/MC62D 0.97 0.95 1.00
(Y*9C/T*9V)*D20 FC/MC62D 0.98 0.96 1.01

Related product manuals