FORM 201.24-EG1
21
YORK INTERNATIONAL
NOTES:
1. KWo = Unit kW Cooling Capacity Output
2. KWi = Compressor kW Input
3. COP = Coefficient of Performance
4. LCWT= Leaving Chilled Water Temperature
5. Ratings based on 0.047 l/s cooler water per kW.
6. For ratings other than 30% glycol, refer to the design 03 dxchill program.
LEAVING CONDENSER WATER TEMPERATURE (°C)
LCWT 30.0 35.0 40.0
(°C) KWo KWi KW COP KWo KWi KW COP KWo KWi KW COP
YCWS0200SC
YCWS0220SC
YCWS0240SC
-8.0 336.2 108.7 445.0 3.1 311.0 123.8 434.0 2.5 289.7 141.9 431.0 2.0
-6.0 371.1 108.7 479.0 3.4 348.0 123.1 471.0 2.8 324.9 140.1 465.0 2.3
-4.0 410.2 109.1 519.0 3.8 386.2 123.0 509.0 3.1 361.1 139.3 500.0 2.6
-2.0 455.6 109.7 565.0 4.2 429.6 123.3 553.0 3.5 403.1 138.9 542.0 2.9
0.0 509.1 110.3 619.0 4.6 481.0 123.8 604.0 3.9 452.3 138.9 591.0 3.3
2.0 569.6 111.1 680.0 5.1 539.1 124.7 663.0 4.3 508.2 139.6 647.0 3.6
4.0 612.8 111.5 724.0 5.5 581.6 125.3 706.0 4.6 549.0 140.1 689.0 3.9
-8.0 366.2 119.5 485.0 3.1 0.0 0.0 468.0 0.0 318.2 155.8 474.0 2.0
-6.0 404.0 119.5 523.0 3.4 378.8 135.2 514.0 2.8 353.0 154.0 507.0 2.3
-4.0 446.9 120.0 566.0 3.7 421.1 135.2 556.0 3.1 393.0 153.1 546.0 2.6
-2.0 496.6 120.7 617.0 4.1 468.0 135.6 603.0 3.5 438.8 152.7 591.0 2.9
0.0 554.4 121.4 675.0 4.6 513.0 136.0 649.0 3.8 492.7 152.8 645.0 3.2
2.0 620.9 122.4 743.0 5.1 587.5 137.2 724.0 4.3 553.6 153.6 707.0 3.6
4.0 668.4 122.9 791.0 5.4 633.7 137.9 771.0 4.6 598.1 154.1 752.0 3.9
-8.0 395.3 130.6 525.0 3.0 363.9 148.8 512.0 2.5 329.5 171.4 501.0 1.9
-6.0 436.1 130.6 566.0 3.3 408.9 147.8 556.0 2.8 381.1 168.4 549.0 2.3
-4.0 482.0 131.1 613.0 3.7 453.6 147.8 601.0 3.1 424.1 167.3 591.0 2.5
-2.0 535.8 131.9 667.0 4.1 504.9 148.1 653.0 3.4 473.4 166.9 640.0 2.8
0.0 598.6 132.7 731.0 4.5 565.4 148.8 714.0 3.8 531.4 167.0 698.0 3.2
2.0 668.8 133.8 802.0 5.0 633.4 150.0 783.0 4.2 597.0 167.9 764.0 3.6
4.0 719.2 134.4 853.0 5.4 681.9 150.8 832.0 4.5 644.5 168.5 813.0 3.8