York Sunline 2000 - Motor and Drive Data - Belt-Drive Blower; Electrical Data W;Direct-Drive Blower; Electrical Data W;Belt-Drive Blower

York Sunline 2000
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODEL
BLOWER
RANGE
(RPM)
MOTOR*
ADJUSTABLE
MOTOR PULLEY
FIXED
BLOWER PULLEY
BELT
HP RPM
FRAME
SIZE
SERVICE
FACTOR
PITCH
DIA.
(in.)
BORE
(in.)
PITCH
DIA.
(in.)
BORE
(in.)
PITCH
LENGTH
(in.)
DESIG-
NATION
BCH 036 790 - 1120 1-1/2 1725 56 1.15 2.4 - 3.4 7/8 5.7 1 37.3 A36
BCH 048 790 - 1120 1-1/2 1725 56 1.15 2.4 - 3.4 7/8 5.7 1 37.3 A36
BCH 060 850 - 1220 1-1/2 1725 56 1.15 2.4 - 3.4 7/8 5.2 1 37.3 A36
*All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any
heating device.
TABLE 8
- MOTOR AND DRIVE DATA w/Belt-Drive Blower
MODEL
BCH
POWER
SUPPLY
VOLTAGE
LIMITATIONS
(SEE NOTE 1)
COMPRESSOR
OUTDOOR
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
(SEE NOTE 2)
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
MIN. MAX. RLA LRA
036
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
19.0
11.9
5.9
4.8
105
85
42
34
1.7
1.7
1.0
1.0
4.4
4.4
2.2
2.2
29.9
21.0
10.6
10.2
45
30
15
15
45
30
15
15
048
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
23.1
14.7
7.7
6.4
105
130
64
52
2.3
2.3
1.4
1.4
5.0
5.0
2.2
2.2
36.1
25.7
13.2
11.6
50
40
20
15
50
40
20
15
060
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
32.1
19.3
10.0
7.9
169
137
62
50
2.3
2.3
1.4
1.4
6.6
6.6
3.3
3.3
49.0
33.0
17.2
14.6
80
50
25
20
80
50
25
20
NOTES: 1. Rated in accordance wtih ARI Standard 110, utilizatin range "A".
2. Dual element, time delay type.
TABLE 9
- ELECTRICAL DATA
w/Direct-Drive Blower Motor
MODEL
BCH
POWER
SUPPLY
VOLTAGE
LIMITATIONS
(SEE NOTE 1)
COMPRESSOR
OUTDOOR
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
(SEE NOTE 2)
AMPS
MAX.
HACR
BREAKER
SIZE,
AMPS
MIN. MAX. RLA LRA
036
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
19.0
11.9
5.9
4.8
105
85
42
34
1.7
1.7
1.0
1.0
5.3
5.3
3.1
3.1
34.8
21.9
11.5
11.1
45
30
15
15
45
30
15
15
048
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
23.1
14.7
7.7
6.4
105
130
64
52
2.3
2.3
1.4
1.4
8.6
5.2
2.6
2.0
39.7
25.9
13.6
11.4
50
40
20
15
50
40
20
15
060
208/230-1-60
208/230-3-60
460-3-60
575-3-60
187
187
414
518
253
253
504
630
32.1
19.3
10.0
7.9
169
137
62
50
2.3
2.3
1.4
1.4
8.6
6.0
3.0
2.4
51.0
32.4
16.9
13.7
80
50
25
20
80
50
25
20
NOTES: 1. Utilization Range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.
w/Belt-Drive Blower Motor
TABLE 10
- ELECTRICAL DATA
511.06-N5Y
Unitary Products Group 11