290699-YIM-B-0607
Unitary Products Group 29
TABLE 16: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
208
208 0.75
240
230 0.92
480
460 0.92
600
575 0.92
TABLE 17: VOLTAGE LIMITATIONS
1
1.
Utilization Range “A” in accordance with ARI Standard
110.
POWER SUPPLY
VOLTAGE
MIN. MAX.
208/230-3-60
187 252
460-3-60
432 504
575-3-60
540 630