York Y34 - Standard Gas Heating Capacities; Temperature Rise; Minimum Heating Cfm; Modulating Gas Heating Capacities

York Y34
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
246653-YTG-E-0108
12 Johnson Controls Unitary Products
TABLE 3: STANDARD GAS HEATING CAPACITIES
GAS HEAT
O
PTION
AVAILABLE ON
M
ODELS
INPUT CAPACITY (MBH)
1
1.
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
O
UTPUT
C
APACITY
(MBH)
2
2.
Blower motor heat not included.
G
AS RATE, CU. FT./HR.
3
3.
Based on a heat content of 1075 Btu/Ft.
3
1ST STAGE TOTAL 1ST STAGE TOTAL
N3 Y32/Y33/Y34 267 267 213 247 247
N5 Y32/Y33/Y34 267 533 426 247 495
N8 Y34 ONLY 267
4
4.
Unit Control Board with 3 heating outputs only. For all other Unit Control Boards the 1st Stage is 533 MBH.
800 638 247 742
TABLE 4: TEMPERATURE RISE
TON
MODULES
123
25 5-35 25-55 -
30 5-35 20-50 -
40 5-30 10-45 25-55
TABLE 5: MINIMUM HEATING CFM
TON
MODULES
123
25 5,644 7,183 -
30 5,644 7,901 -
40 6,584 8,779 13,169
TABLE 6: MODULATING GAS HEATING CAPACITIES
GAS HEAT OPTION
AVAILABLE ON
M
ODELS
INPUT CAPACITY (MBH)
STEPS
O
UTPUT CAPACITY
(MBH)
1
1.
Output Capacity at Full Fire.
G
AS RATE, CU. FT./HR.
M
INIMUM MAXIMUM MINIMUM MAXIMUM
D3
2
2.
Modulating Gas Heat available on CV models only.
Y32/Y33/Y34 69 267 6 213 64 247
D5
2
Y32/Y33/Y34 69 533 12 426 64 495
D8
2
Y34 ONLY 69 800 17 638 64 744