EasyManua.ls Logo

York Y34 - Exhaust Fan Drive Data; Supply Fan Motor and Drive Data

York Y34
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
246653-YTG-E-0108
Johnson Controls Unitary Products 27
TABLE 24: EXHAUST FAN DRIVE DATA
MODEL
BLOWER
RPM
R
ANGE
MOTOR MOTOR PULLEY BLOWER PULLEY BELTS
HP
FRAME
S
IZE
M
OTOR EFF
(S
TD.
M
OTOR)
M
OTOR
E
FF (HI
E
FF OPT)
P
ITCH DIA
(I
NCHES)
B
ORE
(I
NCHES)
P
ITCH DIA
(I
NCHES)
B
ORE
(I
NCHES)
D
ESIGNATION QTY
25 Ton
758 5 213T 87.5 89.5 4.9 1-3/8 11.3 2-3/16 BX63 2
852 7.5 215T 88.5 91.7 5.5 1-3/8 11.3 2-3/16 BX63 2
976 10 215T 89.5 91 6.3 1-5/8 11.3 2-3/16 BX63 2
30 Ton
852 7.5 213T 84 86.5 5.5 1-3/8 11.3 1-11/16 B65 2
976 10 215T 86.5 89.5 6.3 1-3/8 11.3 1-11/16 B65 2
1069 15 254T 85.7 89.5 6.9 1-3/8 11.3 1-11/16 B65 2
40 Ton
852 7.5 184T 84 86.5 5.5 1-3/8 11.3 1-11/16 B65 2
976 10 215T 86.5 89.5 6.3 1-3/8 11.3 1-11/16 B65 2
1069 15 254T 85.7 89.5 6.9 1-3/8 11.3 1-11/16 B65 2
TABLE 25: SUPPLY FAN MOTOR AND DRIVE DATA
1
MODEL
BLOWER
RPM
R
ANGE
MOTOR MOTOR PULLEY BLOWER PULLEY BELTS
HP
F
RAME
SIZE
MOTOR
E
FFICIENCY
(S
TD. MOTOR)
M
OTOR
E
FFICIENCY
(U
LTRA HI
E
FF OPT)
P
ITCH DIA
(I
NCHES)
B
ORE
(I
NCHES)
P
ITCH DIA
(I
NCHES)
B
ORE
(I
NCHES)
D
ESIGNA
TION
QTY
25 Ton
567 7.5 213T 88.5 91.7 4.5 1-3/8 13.9 2-3/16 BX56 2
692 10 215T 89.5 91 5.5 1-3/8 13.9 2-3/16 BX56 2
793 15 254T 91 91.7 6.3 1-5/8 13.9 2-3/16 BX56 2
894 20 256T 91 93 7.1 1-5/8 13.9 2-3/16 BX56 2
30 Ton
617 10 215T 89.5 91 4.9 1-3/8 13.9 2-3/16 BX56 2
743 15 254T 91 91.7 5.9 1-5/8 13.9 2-3/16 BX56 2
856 20 256T 91 93 6.7 1-5/8 13.7 2-3/16 5VX610 2
907 25 284T 91.7 93.6 7.1 1-7/8 13.7 2-3/16 5VX610 2
40 Ton
617 10 215T 89.5 91 4.9 1-3/8 13.9 2-7/16 BX67 2
652 15 254T 91 91.7 5.1 1-5/8 13.7 2-7/16 5VX710 2
728 20 256T 91 93 5.7 1-5/8 13.7 2-7/16 5VX710 2
780 25 284T 91.7 93.6 6.1 1-7/8 13.7 2-7/16 5VX710 2
1.
kW = (BHP X 0.746) / Motor Eff.
MBH = kW X 3.414
MBH = (BHP X 2.546) / Motor Eff.
NOTES: 1) Class I Blowers are limited to 15 HP motors on 25 and 30 Ton units.
2) Class I Blowers are limited to 20 HP motors on the 40 Ton units.
3) Class II Blowers are not HP limited, can use 25 HP.

Table of Contents

Related product manuals