ELECTRICAL NOTES AND LEGEND
1
NOTES:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of
the rated load amps for all other loads included in the circuit, per N.E.C. Article 430.33. If the Factory-mounted
Control Transformer is provided, add the following to the system MCA values in the electrical tables for the
system supplying power to the optional transformer. -50, add 1.75 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included
in the circuit, per N.E.C. Article 440.12 (A) 1.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not
recommended in ap pli ca tions where brown outs, frequent starting and stopping of the unit, and/or op er a tion at
ambient tem per a tures in excess of 95°F is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated
load amps for all other loads included in the circuit, per N.E.C. Article 440.22.
5. Circuit breakers must be U.L. listed and CSA certi ed and maximum size is based on 225% of the rated load
amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Ex cep tion:
YCAL0043 and YCAL0057 must have the optional factory overloads installed to use a standard circuit breaker.
Oth er wise, an HACR-type circuit break ers must be used. Maximum HACR circuit break er rating is based on
225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included
in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the
unit wiring lugs. The (2) preceding the wire range indicates the number of ter mi na tion points available per phase
of the wire range speci ed. Actual wire size and number of wires per phase must be determined based on the
National Elec tri cal Code, using copper con nec tors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compressor system to accommodate a eld grounding con duc tor per N.E.C.
Table 250.122. A control circuit grounding lug is also supplied.
8. The supplied disconnect is a “Disconnecting Means” as de ned in the N.E.C. 100.I, and is intended for iso lat ing
the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not
intended to be a Load Break Device.
9. Field Wiring by others which complies to the National Electrical Code and Local Codes.
VOLTAGE CODE
-50 = 380/415-3-50
LEGEND
ACR-LINE ACROSS -THE-LINE START
C.B. CIRCUIT BREAKER
D.E. DUAL ELEMENT FUSE
DISC SW DISCONNECT SWITCH
FACT MOUNT CB FACTORY-MOUNTED CIRCUIT BREAKER
FLA FULL LOAD AMPS
HZ HERTZ
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MIN NF MINIMUM NON FUSED
RLA RATED LOAD AMPS
S.P. WIRE SINGLE-POINT WIRING
UNIT MTD SERV SW
UNIT MOUNTED SERVICE (NON-FUSED
DISCONNECT SWITCH)
LRA LOCKED ROTOR AMPS
Field Wiring
Factory Wiring
LEGEND: