YORK INTERNATIONAL
26
FORM 150.62-NM7 (103)
ELECTRICAL DATA – MULTIPLE POINT POWER SUPPLY CONNECTIONS – YCAL0287E_ - YCAL0377E_
TABLE 5 – MULTIPLE POINT POWER SUPPLY CONNECTIONS
Installation
(Two Field Provided Power Supply Circuits to the chiller. Field connections to Factory Provided Terminal Blocks (standard), Non-Fused Discon-
nect Switches (optional), or Individual System Circuit Breakers (optional) per electrical system
)
MODEL
YCAL
VOLT HZ
SYSTEM #1 FIELD SUPPLIED WIRING SYSTEM #1 COMPRESSOR & FAN
MCA
1
MIN
N/F
DISC
SW
2
D.E. FUSE CKT. BKR.
5
INCOMING (LUGS) WIRE RANGE
6
COMPR. #1 COMPR. #2 COMPR. #3 FANS
TERMINAL
BLOCK
(std)
NF
DISC.
SWITCHES
(opt)
CIR
BREAKERS
(opt)
MIN
3
MAX
4
MIN MAX RLA LRA RLA LRA RLA LRA QTY
FLA
(EA)
0287 380/415 50 118 150 150 150 150 150 # 14 - 2/0 # 6 - 350 # 6 - 350 32.6 215 32.6 215 32.6 215 3 3.8
0317 380/415 50 118 150 150 150 150 150 # 14 - 2/0 # 6 - 350 # 6 - 350 32.6 215 32.6 215 32.6 215 3 3.8
0347 380/415 50 156 200 175 200 175 200 # 6 - 400 # 6 - 350 # 6 - 350 44.2 270 44.2 270 44.2 270 3 3.8
0377 380/415 50 156 200 175 200 175 200 # 6 - 400 # 6 - 350 # 6 - 350 44.2 270 44.2 270 44.2 270 3 3.8