YORK INTERNATIONAL
38
FORM 150.62-NM7 (103)
Installation
BB
(*12 7/8") (** 14 1/4")
4 1/2"
4 1/2"
3 1/2"
2"
1 3/4" TYP.
6 1/2"
1 3/8"
5 7/8"
1 3/4" TYP.
51 1/2"
VIEW A-A
VIEW B-B
(4) 1/2" CONDUIT K.O.'S
(2) 2",1 1/2" CONDUIT K.O.'S
POWER ENTRY
(4) 1/2" CONDUIT K.O.'S
CONTROL ENTRY
CONNECTION)
UNIT TO COOLER
2 1/2" (EDGE OF
DIMENSIONS - YCAL0073-YCAL0107 (EN GLISH)
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in un pre dict able air ow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pres sure safety cutouts;
however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
LD08750
* Refers to Model YCAL0073
** Refers to Model YCAL0087 and YCAL0107