77
FORM 150.62-NM7 (103)
PRINT Key
The PRINT key allows the operator to obtain a print out 
of real-time system operating data or a history printout 
of sys tem data at the “instant of the fault” on the last six 
faults which oc curred on the unit. An optional printer is 
re quired for the printout.
OPERATING DATA PRINTOUT
Pressing the PRINT key and then OPER DATA key al-
 lows the operator to obtain a printout of current system 
operating parameters. When the OPER DATA key is 
pressed, a snapshot will be taken of sys tem op er at ing 
con di tions and panel pro gram ming se lec tions. This data 
will be temporarily stored in memory and trans mis sion 
of this data will begin to the printer. A sam ple Operating 
Data printout is shown below. (Note: Not all values are 
printed for all models.)
See Service And Troubleshooting sec tion 
for  Print er  In stal la tion  in for ma tion.
 
YORK INTERNATIONAL COR PO RA TION
MILLENNIUM LIQUID CHILLER
UNIT STATUS
2:04PM 01 JAN 02
SYS 1  NO COOLING LOAD
SYS 2  COMPRESSORS RUNNING 2
OPTIONS
CHILLED LIQUID  WATER
AMBIENT CONTROL  STANDARD
LOCAL/REMOTE MODE  REMOTE
CONTROL MODE  LEAVING LIQUID
LEAD/LAG CONTROL  AUTOMATIC
FAN CONTROL  AMB & DSCH PRESS
CURRENT FEEDBACK  NONE
SOFT START  ENABLED
EXPANSION VALVE       THERMOSTATIC 
PROGRAM VALUES
DSCH PRESS CUTOUT  395 PSIG
SUCT PRESS CUTOUT  44 PSIG
LOW AMBIENT CUTOUT  25.0 DEGF
LEAVING LIQUID CUTOUT  36.0 DEGF
ANTI RECYCLE TIME  600 SECS
FAN CONTROL ON PRESS  240 PSIG
FAN DIFF OFF PRESS  80 PSIG
NUMBER OF COMPRESSORS  6
NUMBER OF FANS PER SYSTEM         4 
UNIT TRIP VOLTS                 3.0
REFRIGERANT TYPE  R-22
REMOTE UNIT ID PROGRAMMED  2
UNIT DATA
RETURN LIQUID TEMP  58.2 DEGF
LEAVING LIQUID TEMP  53.0 DEGF
COOLING RANGE  42.0 +/- 2.0 DEGF
AMBIENT AIR TEMP  74.8 DEGF
LEAD SYSTEM  SYS 2
EVAPORATOR PUMP  ON
EVAPORATOR HEATER  OFF
ACTIVE REMOTE CONTROL  NONE
UNIT  XXX.X AMPS  X.X VOLTS
SOFTWARE VERSION  C.MMC.03.03
SYSTEM 1 DATA
COMP STATUS     1=OFF 2=OFF 3=OFF
RUN TIME       0- 0- 0- 0 D-H-M-S
SUCTION PRESSURE          66 PSIG
DISCHARGE PRESSURE       219 PSIG
SUCTION TEMPERATURE     52.8 DEGF
SAT SUCTION TEMP        40.0 DEGF
SUCTION SUPERHEAT       12.8 DEGF
COOLER INLET REFRIG     31.6 DEGF
LIQUID LINE SOLENOID          OFF
HOT GAS BYPASS VALVE          OFF
CONDENSER FAN STAGES          OFF
EEV OUTPUT                  0.0 %
SYSTEM       XXX.X AMPS X.X VOLTS
SYSTEM 2 DATA
COMP STATUS   1=OFF, 2=OFF, 3=OFF
SUCTION PRESSURE          51 PSIG
DISCHARGE PRESSURE       157 PSIG
SUCTION TEMPERATURE     44.3 DEGF
SAT SUCTION TEMP        32.1 DEGF
SUCTION SUPERHEAT       12.2 DEGF
COOLER INLET REFRIG     31.6 DEGF
LIQUID LINE SOLENOID           ON
CONDENSER FAN STAGE             3
EEV OUTPUT                   0.0%
SYSTEM      XXX.X AMPS  X.X VOLTS
DAILY SCHEDULE
S M T W T F S           *=HOLIDAY
MON START=00:00AM    STOP=00:00AM
TUE START=00:00AM    STOP=00:00AM
WED START=00:00AM    STOP=00:00AM
THU START=00:00AM    STOP=00:00AM
FRI START=00:00AM    STOP=00:00AM
SAT START=00:00AM    STOP=00:00AM
HOL START=00:00AM    STOP=00:00AM
2