YORK INTERNATIONAL
87
FORM 150.62-NM7 (103)
The TOTAL NUMBER OF COM PRES SORS is the total 
quantity of compressors in the chiller, and de ter mines 
the stag es of cool ing avail able. Note in Ta ble 20, the 
chill er may have sin gle or dual sys tems.
This MUST be programmed correctly 
to as sure prop er chiller operation.
A single system chiller MUST have a 
jumper be tween terminals 13 - 17 on 
terminal block CTB1. If the jumper 
is not in stalled, the unit will act as a 
2-system chill er. The jumper is only 
checked by the micro at unit pow er-up. 
If the jump er is re moved, power must 
be re moved and re-applied to reg is ter 
the change in memory.
The number of fans per system is pro grammed for the 
total number of fans on each system, or the total num ber 
on the chiller di vid ed by 2. This is only pro gram ma ble on 
YCAL0287 - YCAL0377 chill ers.
This MUST be programmed correctly 
to as sure prop er chiller operation.
  T  O T A  L  N U M B  E  R O  F
 C O M  P  R  E S  S O R  S  = 6  
2
 N U M B E  R  O F  F  A  N S
 P  E  R S  Y S  T  E M  =  X 
SYSTEM TRIP VOLTS
For individual system high current trip programming on 
chillers:
  •   Add the sum of the compressor and fan RLA’s in 
the system 
  •  Multiply the sum by 1.25
  •  Divide by 225A
 •   The resulting voltage is the value that should be 
programmed
For example, if fan and compressor RLA’s total 100A:
 5V x 100A        
x        1.25  =
         625VA 
=   2.8V
 225A  225A 
The programmed value will be 2.8V. A similar cal cu la tion 
and programming will be necessary for the other system 
in a 2-system chiller.
UNIT TRIP VOLTS
For total chiller high current trip programming on chill-
ers:
  •    Add the sum of all the the compressor and fan RLA’s 
in the chiller
  •  Multiply the sum by 1.25
  •  Divide by 225A
 •   The resulting voltage is the value that should be 
programmed
For example, if fan and compressor RLA’s total 180A:
 5V x 180A        
x        1.25  =
 1125VA  
=   5.0V
 225A  225A 
The programmed value will be 5.0V.
When communications is required with a BAS or Op-
 ti V iew Panel, individual unit IDs are necessary for com-
 mu ni ca tions with specifi c chillers on a single RS-485 
line. ID 0-7 is selectable.
             S  Y  S    X    T  R  I  P    V  O  L  T  S
          =  X .  X      V  O  L  T  S
             U  N  I  T       T  R  I  P    V  O  L  T  S
                         =  X .  X      V  O  L  T  S
Depending on the option, the trip voltage for a 
specific sys tem or unit high current trip (See page 
80) can be programmed. It also cal i brates the current 
read out un der the OPER DATA key. The approximate 
programmed value is calculated using the following 
formulas:
       R  E  M  O  T  E    U  N  I  T    I  D
 P  R  O  G  R  A  M  M  E  D    =    X