FORM 150.63-EG1
Electrical Data
MODEL
YCUL
VOLT HZ
SYSTEM #1 FIELD SUPPLIED WIRING
MCA
1
MIN N/F
DISC SW
2
D.E. FUSE CKT. BKR.
5
INCOMING (LUGS) WIRE RANGE
6
MIN
3
MAX
4
MIN MAX
TERMINAL BLOCK
(std)
NF DISC. SWITCHES
(opt)
CIR BREAKERS
(opt)
0096
200 60 251 400 300 350 300 350 # 6 - 400 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
230 60 233 250 300 300 300 300 # 6 - 400 (1) # 6 - 350 (1 or 2) 3/0 - 500
380 60 135 150 150 175 150 175 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
460 60 111 150 125 150 125 150 # 14 - 2/0 (1) # 6 - 350 (1) # 3 - 3/0
575 60 89 100 100 110 100 110 # 14 - 2/0 (1) # 6 - 350 (1) # 10 - 1/0
0100
200 60 251 400 300 350 300 350 # 6 - 400 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
230 60 233 250 300 300 300 300 # 6 - 400 (1) # 6 - 350 (1 or 2) 3/0 - 500
380 60 135 150 150 175 150 175 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
460 60 111 150 125 150 125 150 # 14 - 2/0 (1) # 6 - 350 (1) # 3 - 3/0
575 60 89 100 100 110 100 110 # 14 - 2/0 (1) # 6 - 350 (1) # 10 - 1/0
0106
200 60 274 400 300 300 300 300 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
230 60 254 400 300 300 300 300 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
380 60 148 200 175 175 175 175 # 14 - 2/0 (1) # 6 - 350 (1) # 3 - 3/0
460 60 122 150 150 150 150 150 # 14 - 2/0 (1) # 6 - 350 (1) # 10 - 1/0
575 60 98 150 110 110 110 110 # 14 - 2/0 (1) # 10 - 1/0 (1) # 10 - 1/0
0120
200 60 274 400 300 300 300 300 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
230 60 254 400 300 300 300 300 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
380 60 148 200 175 175 175 175 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
460 60 122 150 150 150 150 150 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
575 60 98 150 110 110 110 110 # 14 - 2/0 (1) # 6 - 350 (1) # 3 - 3/0
0130
200 60 359 400 400 450 400 450 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
230 60 333 400 400 400 400 400 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
380 60 194 250 225 225 225 225 # 6 - 400 (1) # 6 - 350 (1) # 6 - 350
460 60 159 200 175 200 175 200 # 6 - 400 (1) # 6 - 350 (1) # 6 - 350
575 60 128 150 150 150 150 150 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
MODEL
YCUL
VOLT HZ
SYSTEM #2 FIELD SUPPLIED WIRING
MCA
1
MIN N/F
DISC SW
2
D.E. FUSE CKT. BKR.
5
INCOMING (LUGS) WIRE RANGE
6
MIN
3
MAX
4
MIN MAX
TERMINAL BLOCK
(std)
NF DISC. SWITCHES
(opt)
CIR BREAKERS
(opt)
0096
200 60 191 200 225 250 225 250 # 6 - 400 (1) # 6 - 350 (1) # 6 - 350
230 60 178 200 200 225 200 225 # 6 - 400 (1) # 6 - 350 (1) # 6 - 350
380 60 104 150 125 125 125 125 # 14 - 2/0 (1) # 6 - 350 (1) # 3 - 3/0
460 60 85 100 100 110 100 110 # 14 - 2/0 (1) # 10 - 1/0 (1) # 10 - 1/0
575 60 68 100 80 90 80 90 # 14 - 2/0 (1) # 10 - 1/0 (1) # 10 - 1/0
0100
200 60 251 400 300 350 300 350 # 6 - 400 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
230 60 233 250 300 300 300 300 # 6 - 400 (1) # 6 - 350 (1 or 2) 3/0 - 500
380 60 135 150 150 175 150 175 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
460 60 111 150 125 150 125 150 # 14 - 2/0 (1) # 6 - 350 (1) # 3 - 3/0
575 60 89 100 100 110 100 110 # 14 - 2/0 (1) # 6 - 350 (1) # 10 - 1/0
0106
200 60 259 400 300 350 300 350 # 6 - 400 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
230 60 241 250 300 300 300 300 # 6 - 400 (1) # 6 - 350 (1 or 2) 3/0 - 500
380 60 140 150 175 175 175 175 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
460 60 115 150 150 150 150 150 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
575 60 92 100 110 125 110 125 # 14 - 2/0 (1) # 6 - 350 (1) # 3 - 3/0
0120
200 60 274 400 300 300 300 300 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
230 60 254 400 300 300 300 300 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
380 60 148 200 175 175 175 175 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
460 60 122 150 150 150 150 150 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
575 60 98 150 110 110 110 110 # 14 - 2/0 (1) # 6 - 350 (1) # 3 - 3/0
0130
200 60 374 400 300 300 300 300 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
230 60 354 400 300 300 300 300 (2) # 4 - 500 (1 or 2) 3/0 - 500 (1 or 2) 3/0 - 500
380 60 148 200 175 175 175 175 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
460 60 122 150 150 150 150 150 # 14 - 2/0 (1) # 6 - 350 (1) # 6 - 350
575 60 98 150 110 110 110 110 # 14 - 2/0 (1) # 6 - 350 (1) # 3 - 3/0
YCUL0096 - YCUL0130
MULTIPLE POINT POWER SUPPLY CONNECTIONS (see Fig. 3)
(Two Field Provided Power Supply Circuits to the condensing unit. Field connections to Factory Provided Terminal Blocks (standard), Non-Fused Disconnect
Switches (optional) or Individual System Circuit Breakers (optional) per electrical system.)
See Notes on page 100