Quit condition of oil return:
1 minute later after oil return is over
& Td‐Tcm>30℃
OR OR Ts ‐Tc>30℃
Tc<‐35℃
Max. 10 minutes
Oil return procedure in heating mode:
Quit condition of oil return
Max. 9 minutes(E )
OR OR Td‐Tcm<20℃ for 30s(5 minutes later, begin to count)
&
T s ‐Tc<15℃ for 30 S(5 minutes later, begin to count)
Running for min. 5 minutes(E )
Send oil return signal oil return beginning oil return over
Inverter compressor indicated FQY 60s oil return frequency 120s
Soft startup
0HZ
0HZ
5s
outdoor motor auto auto
auto(TC control)
4-way valve ON
OFF
15s
450pulse 450 pulse
300pulse (E )
PMV auto open angel auto open angle
all indoor motor ON
OFF anti-freeze startup