EasyManuals Logo

York YT Millennium User Manual

York YT Millennium
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #119 background imageLoading...
Page #119 background image
FORM 160.55-O1 (920)
119
YORK INTERNATIONAL
FIG. 45 – CONTINUED
3
Remote Modem Current Limit = 100 %
Pulldown Demand Limit = 100 %
Pulldown Demand Time = 0 Min
[Skip the following section if Motor Type is not Mod A
SSS]
Liquid-Cooled Solid State Starter
-------------------------------------------------------------------------
Local Motor Current Limit = 100 %
Remote ISN Current Limit = 100 %
Remote Analog Current Limit = 100 %
Remote Digital Current Limit = 100 %
Remote Modem Current Limit = 100 %
Pulldown Demand Limit = 100 %
Pulldown Demand Time = 0 Min
Scale/Model = 600 V, 281 A
Supply Voltage Range = Disabled
Full Load Amps = 150 A
Current Imbalance Check = Disabled
[Skip the following section if Motor Type is not Mod B
SSS]
Liquid-Cooled Solid State Starter
-------------------------------------------------------------------------
Local Motor Current Limit = 100 %
Remote ISN Current Limit = 100 %
Remote Analog Current Limit = 100 %
Remote Digital Current Limit = 100 %
Remote Modem Current Limit = 100 %
Pulldown Demand Limit = 100 %
Pulldown Demand Time = 0 Min
Starter Model = 33L
Voltage Range = Disabled
Full Load Amps = 215 A
Starting Current = 1460 A
Open SCR = Disabled
[Skip the following section if Motor Type is not VSD]
Variable Speed Drive
-------------------------------------------------------------------------
Local Motor Current Limit = 100 %
Remote ISN Current Limit = 100 %
Remote Analog Current Limit = 100 %
Remote Digital Current Limit = 100 %
Remote Modem Current Limit = 100 %
Pulldown Demand Limit = 100 %
Pulldown Demand Time = 0 Min
Motor HP = 351 HP
Power Line Frequency = 60 Hz
[Skip the following section if Motor Type is not VSD]
Harmonic Filter Data
-------------------------------------------------------------------------
Filter Operation = Enabled
Motor HP = 351 HP
YORK SCHEDULE
CHILLER ID 0
© 1997 - 1999 YORK international corporation
mon 21 jun 1999 1:28:25 pm
schedule = OFF
Standard Schedule
---------------------------------------------------------------------------
Sun StarT = O Stop = O
MOn Start = 06:00 AM Stop = 06:00 PM
Tue Start = 06:00 AM Stop = 06:00 PM
Wed Start = 06:00 AM Stop = 06:00 PM
Th u Start = 06:00 AM Stop = 06:00 PM
Fri Start = 06:00 AM Stop = 06:00 PM
Sat Start = O Stop = O
Exception Days
---------------------------------------------------------------------------
15 jul 1999 start = 08:00 am stop = 08:00 pm
16 jul 1999 start = 08:00 am stop = 08:00 pm
17 jul 1999 start = 08:00 am stop = 08:00 pm
18 jul 1999 start = 08:00 am stop = 08:00 pm
FIG. 46 – SAMPLE PRINTOUT
(SCHEDULE REPORT)