Johnson Controls Unitary Products 29
505591-YTG-A-0909
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. YZH02411(C)
INDOOR COIL MODEL NO. FC/MC/PC48D + MV12D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 600 650 700
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 19.7 20.0 19.9 22.0 23.6 19.7 20.0 19.9 22.0 23.6 19.7 20.0 19.9 22.0 23.6
S.C. 19.7 19.2 15.7 15.8 13.0 19.7 19.2 15.7 15.8 13.0 19.7 19.2 15.7 15.8 13.0
K.W. 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
75
T.C. 18.9 19.0 18.9 21.0 22.6 18.9 19.0 18.9 21.0 22.6 18.9 19.0 18.9 21.0 22.6
S.C. 18.9 18.5 15.4 15.4 12.5 18.9 18.5 15.4 15.4 12.5 18.9 18.5 15.4 15.4 12.5
K.W. 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
85
T.C. 18.1 18.0 18.0 20.0 21.7 18.1 18.0 18.0 20.0 21.7 18.1 18.0 18.0 20.0 21.7
S.C. 18.1 17.7 15.0 15.0 12.1 18.1 17.7 15.0 15.0 12.1 18.1 17.7 15.0 15.0 12.1
K.W. 1.0 1.0 1.1 1.1 1.1 1.0 1.0 1.1 1.1 1.1 1.0 1.0 1.1 1.1 1.1
95
T.C. 17.4 17.0 17.1 18.9 20.7 17.4 17.0 17.1 18.9 20.7 17.4 17.0 17.1 18.9 20.7
S.C. 17.4 17.0 14.6 14.6 11.7 17.4 17.0 14.6 14.6 11.7 17.4 17.0 14.6 14.6 11.7
K.W. 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
105
T.C. 16.2 15.9 15.6 17.4 19.1 16.2 15.9 15.6 17.4 19.1 16.2 15.9 15.6 17.4 19.1
S.C. 16.2 15.9 13.9 14.0 11.1 16.2 15.9 13.9 14.0 11.1 16.2 15.9 13.9 14.0 11.1
K.W. 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
115
T.C. 15.0 14.9 14.1 15.9 17.6 15.0 14.9 14.1 15.9 17.6 15.0 14.9 14.1 15.9 17.6
S.C. 15.0 14.9 13.3 13.5 10.5 15.0 14.9 13.3 13.5 10.5 15.0 14.9 13.3 13.5 10.5
K.W. 1.6 1.6 1.5 1.6 1.6 1.6 1.6 1.5 1.6 1.6 1.6 1.6 1.5 1.6 1.6
125
T.C. 13.8 13.8 12.7 14.3 16.0 13.8 13.8 12.7 14.3 16.0 13.8 13.8 12.7 14.3 16.0
S.C. 13.8 13.8 12.7 13.0 10.0 13.8 13.8 12.7 13.0 10.0 13.8 13.8 12.7 13.0 10.0
K.W. 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
AHX36 – 0.93 0.86 1.03
AV*36 – 0.98 0.96 0.98
MV12B FC/MC43B 0.98 0.96 0.97
MV12D FC/MC60D 1.00 1.00 1.00
Furnace Coil T.C. S.C. KW
T*(8,L)X*A12 FC/MC/PC37A 0.99 0.99 0.99
T*(8,L)X*B12 FC/MC/PC43B 1.02 1.04 0.98
T*(8,L)X*C16 FC/MC/PC43C 0.99 0.99 1.00
T*9X*B12 FC/MC/PC43B 0.99 0.99 0.99
T*9X*C16 FC/MC/PC43C 0.99 0.99 1.00
T*9X*C16 FC/MC/PC48C 1.01 1.03 1.00
T*(8,L)X*B12 HC42 0.99 1.00 1.04
T*(8,L)X*C16 HC42 1.01 1.03 1.01
T*9X*B12 HC42 1.00 0.98 1.04
T*9X*C16 HC42 1.01 1.03 1.01
T*9X*C16 UC48C 1.00 1.03 1.00
(Y*(8,L)C/T*8V)*A12 FC/MC/PC30A 0.97 0.93 1.01
(Y*(8,L)C/T*8V)*B12 FC/MC/PC30B 0.96 0.91 0.99
(Y*9C/T*9V)*B12 FC/MC/PC30B 0.96 0.91 1.00
(Y*(8,L)C/T*8V)*A12 FC/MC/PC32A 0.94 0.89 1.01
(Y*(8,L)C/T*8V)*B12 FC/MC/PC35B 0.94 0.86 0.99
(Y*9C/T*9V)*B12 FC/MC/PC35B 0.94 0.89 1.00
(Y*(8,L)C/T*8V)*A12 FC/MC/PC36A 0.96 0.93 1.00
(Y*(8,L)C/T*8V)*B12 FC/MC/PC36B 0.95 0.88 0.99
(Y*9C/T*9V)*B12 FC/MC/PC36B 0.96 0.93 1.00
(Y*(8,L)C/T*8V)*A12 FC/MC/PC37A 0.97 0.93 1.01
(Y*(8,L)C/T*8V)*B12 FC/MC/PC43B 0.95 0.87 0.99
(Y*9C/T*9V)*B12 FC/MC/PC43B 0.96 0.90 1.00
(Y*(8,L)C/T*8V)*B12 HC42 0.96 0.88 1.00
(Y*9C/T*9V)*B12 HC42 0.97 0.91 1.00
(Y*(8,L)C/T*8V)*A12 HD36 0.95 0.89 1.00
(Y*(8,L)C/T*8V)*B12 HD36 0.92 0.83 0.99
(Y*9C/T*9V)*B12 HD36 0.95 0.89 1.00
(Y*(8,L)C/T*8V)*A12 UC30A 0.97 0.93 1.01
(Y*(8,L)C/T*8V)*B12 UC30B 0.97 0.92 0.99
(Y*9C/T*9V)*B12 UC30B 0.96 0.92 1.00
(Y*(8,L)C/T*8V)*A12 UC36A 0.96 0.92 1.00
(Y*(8,L)C/T*8V)*B12 UC36B 0.94 0.87 0.99
(Y*9C/T*9V)*B12 UC36B 0.96 0.92 1.00
Furnace Coil T.C. S.C. KW