5167531-YIM-J-1019
Johnson Controls Ducted Systems 21
120
(10)
208 16.0 110.0 24.9 3.0 6.8 5.5 0.0
None-- -48.954.460 70
E18 13.5 2 37.5 55.3 62.2 60 70
E24 18.0 2 50.0 71.0 77.8 80 80
E36 25.5 2 70.8 97.0 103.9 100 110
E54 40.6 2 112.7 149.4 156.2 150 175
230 16.0 110.0 24.9 3.0 6.8 5.5 0.0
None-- -48.954.460 70
E18 18.0 2 43.3 62.6 69.5 70 70
E24 24.0 2 57.7 80.7 87.5 90 90
E36 34.0 2 81.8 110.7 117.6 125 125
E54 54.0 2 129.9 138.4 145.3 150 175
460 7.8 52.0 12.1 1.6 3.4 2.2 0.0
None-- -24.226.430 30
E18 18.0 2 21.7 31.3 34.1 35 35
E24 24.0 2 28.9 40.3 43.1 45 45
E36 34.0 2 40.9 55.4 58.1 60 60
E54 54.0 2 65.0 69.2 72.0 80 80
575 5.7 38.9 8.9 1.4 2.4 1.8 0.0
None-- -17.919.720 25
E18 18.0 2 17.3 24.7 26.9 25 30
E24 24.0 2 23.1 31.9 34.1 35 35
E36 34.0 2 32.7 43.9 46.1 45 50
E54 54.0 2 52.0 55.0 57.2 60 60
150
(12.5)
208 22.4 149.0 35.0 2.1 9.6 5.5 0.0
None-- -68.473.990 90
E18 13.5 2 37.5 68.4 73.9 90 90
E24 18.0 2 50.0 74.5 81.3 90 90
E36 25.5 2 70.8 100.5 107.4 110 110
E54 40.6 2 112.7 152.9 159.7 175 175
230 22.4 149.0 35.0 2.1 9.6 5.5 0.0
None-- -68.473.990 90
E18 18.0 2 43.3 68.4 73.9 90 90
E24 24.0 2 57.7 84.2 91.0 90 100
E36 34.0 2 81.8 114.2 121.1 125 125
E54 54.0 2 129.9 141.9 148.8 175 175
460 10.6 75.0 16.5 1.3 4.7 2.2 0.0
None-- -33.635.840 45
E18 18.0 2 21.7 33.6 35.8 40 45
E24 24.0 2 28.9 42.0 44.7 45 45
E36 34.0 2 40.9 57.0 59.7 60 60
E54 54.0 2 65.0 70.8 73.6 80 80
575 7.7 54.0 12.0 0.7 3.6 1.8 0.0
None-- -23.625.430 30
E18 18.0 2 17.3 26.2 28.4 30 30
E24 24.0 2 23.1 33.4 35.6 35 40
E36 34.0 2 32.7 45.4 47.6 50 50
E54 54.0 2 52.0 56.5 58.7 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZR078-150 standard motor - without powered convenience outlet (continued)
Size
(tons)
Volt
Compressors
(each)
OD fan
motors
(each)
Supply
blower
motor
Pwr exh
motor
Pwr
conv
outlet
Electric heat option
MCA
1
(amps)
MCA
1
with pwr
exh (amps)
Max fuse
2
/
breaker
3
size
(amps)
Max fuse
2
/
breaker
3
size with
pwr exh
(amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps