5167531-YIM-J-1019
42 Johnson Controls Ducted Systems
Airflow performance
Table 18: Airflow performance - side duct application
ZR078 (6.5 ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP and field supplied drive Standard 1.5 HP and drive High static 2 HP and drive
1800 778 0.37 838 0.56 895 0.73 951 0.88 1005 1.01 1059 1.13 1112 1.25 1166 1.3612211.4712781.59
2000 803 0.50 864 0.69 921 0.85 977 1.00 1031 1.14 1085 1.26 1138 1.37 1192 1.4912471.6013041.72
2200 833 0.64 893 0.83 951 1.00 1006 1.14 1061 1.28 1114 1.40 1168 1.51 1221 1.6312761.7413331.86
2400 866 0.80 926 0.99 984 1.15 1039 1.30 1094 1.43 1147 1.56 1201 1.67 1254 1.7813091.9013662.02
2600 902 0.97 962 1.16 1020 1.33 1076 1.47 1130 1.61 1183 1.73 1237 1.85 1291 1.9613462.0714022.19
2800 941 1.16 1002 1.35 1059 1.52 1115 1.67 1169 1.80 1222 1.92 1276 2.04 1330 2.15 1385 2.26 - -
3000 983 1.37 1043 1.56 1101 1.73 1157 1.88 1211 2.01 1264 2.13 1318 2.25 - - - - --
3200 1028 1.60 1088 1.79 1145 1.95 1201 2.10 1255 2.24 - - - - - -----
340010741.8411342.0311922.20--------------
2 HP and field supplied drive
ZR090 (7.5 ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP and field supplied drive Standard 1.5 HP and drive High static 3 HP and drive
2000 803 0.50 864 0.69 921 0.85 977 1.00 1031 1.14 1085 1.26 1138 1.37 1192 1.4912471.6013041.72
2200 833 0.64 893 0.83 951 1.00 1006 1.14 1061 1.28 1114 1.40 1168 1.51 1221 1.6312761.7413331.86
2400 866 0.80 926 0.99 984 1.15 1039 1.30 1094 1.43 1147 1.56 1201 1.67 1254 1.7813091.9013662.02
2600 902 0.97 962 1.16 1020 1.33 1076 1.47 1130 1.61 1183 1.73 1237 1.85 1291 1.9613462.0714022.19
2800 941 1.16 1002 1.35 1059 1.52 1115 1.67 1169 1.80 1222 1.92 1276 2.04 1330 2.15 1385 2.26 1442 2.38
3000 983 1.37 1043 1.56 1101 1.73 1157 1.88 1211 2.01 1264 2.13 1318 2.25 1372 2.36 1427 2.47 1483 2.59
3200 1028 1.60 1088 1.79 1145 1.95 1201 2.10 1255 2.24 1309 2.36 1362 2.47 14162.5914712.7015282.82
3400 1074 1.84 1134 2.03 1192 2.20 1248 2.35 1302 2.48 1355 2.60 1409 2.72 14632.8315182.9415743.06
3600 1123 2.10 1183 2.29 1241 2.46 1297 2.61 1351 2.74 1404 2.86 1458 2.98 15123.0915673.2116233.32
3800 1174 2.38 1234 2.57 1292 2.74 1348 2.88 1402 3.02 1455 3.14 1509 3.26 15623.37----
3 HP and field supplied drive
ZR102 (8.5 ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP and field
supplied drive
Standard 2 HP and drive High static 3 HP and drive
2200 684 0.48 735 0.67 783 0.84 829 1.01 874 1.17 918 1.32 960 1.48 1001 1.63 1041 1.78 1081 1.94
2400 695 0.58 745 0.76 793 0.94 840 1.11 885 1.27 928 1.42 970 1.57 1011 1.73 1052 1.88 1091 2.04
2600 706 0.67 756 0.86 805 1.04 851 1.20 896 1.36 939 1.52 981 1.67 1023 1.82 1063 1.98 1103 2.13
2800 719 0.78 769 0.96 817 1.14 863 1.31 908 1.47 952 1.62 994 1.78 1035 1.93 1075 2.08 1115 2.24
3000 732 0.89 782 1.08 831 1.25 877 1.42 922 1.58 965 1.74 1007 1.89 1049 2.04 10892.1911282.35
3200 747 1.02 797 1.21 846 1.38 892 1.55 937 1.71 980 1.86 1023 2.02 1064 2.17 11042.3211442.48
3400 764 1.16 814 1.35 862 1.53 909 1.69 954 1.85 997 2.01 1039 2.16 1080 2.31 11212.4711602.62
3600 783 1.33 833 1.51 881 1.69 927 1.86 972 2.02 1016 2.17 1058 2.32 1099 2.48 11392.6311792.79
3800 803 1.51 853 1.69 901 1.87 948 2.04 992 2.20 1036 2.35 1078 2.50 1119 2.66 11592.8111992.97
4000 825 1.71 875 1.89 923 2.07 970 2.23 1014 2.39 1058 2.55 1100 2.70 1141 2.8611813.0112213.16
4200 849 1.92 899 2.11 947 2.29 993 2.45 1038 2.61 1082 2.77 1124 2.92 1165 3.0712053.2312453.38
3 HP and field supplied drive