Johnson Controls Ducted Systems 43
ZR120 (10 ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP and field supplied drive Standard 2 HP and drive High static 3 HP and drive
2600 706 0.67 756 0.86 805 1.04 851 1.20 896 1.36 939 1.52 981 1.67 1023 1.82 1063 1.98 1103 2.13
2800 719 0.78 769 0.96 817 1.14 863 1.31 908 1.47 952 1.62 994 1.78 1035 1.93 1075 2.08 1115 2.24
3000 732 0.89 782 1.08 831 1.25 877 1.42 922 1.58 965 1.74 1007 1.89 1049 2.04 10892.1911282.35
3200 747 1.02 797 1.21 846 1.38 892 1.55 937 1.71 980 1.86 1023 2.02 1064 2.17 11042.3211442.48
3400 764 1.16 814 1.35 862 1.53 909 1.69 954 1.85 997 2.01 1039 2.16 1080 2.31 11212.4711602.62
3600 783 1.33 833 1.51 881 1.69 927 1.86 972 2.02 1016 2.17 1058 2.32 1099 2.48 11392.6311792.79
3800 803 1.51 853 1.69 901 1.87 948 2.04 992 2.20 1036 2.35 1078 2.50 1119 2.66 11592.8111992.97
4000 825 1.71 875 1.89 923 2.07 970 2.23 1014 2.39 1058 2.55 1100 2.70 1141 2.8611813.0112213.16
4200 849 1.92 899 2.11 947 2.29 993 2.45 1038 2.61 1082 2.77 1124 2.92 1165 3.0712053.2312453.38
4400 874 2.16 924 2.35 972 2.52 1019 2.69 1064 2.85 1107 3.01 1149 3.16 1190 3.31----
4600 901 2.42 952 2.61 1000 2.78 1046 2.95 1091 3.11 1134 3.26 1177 3.42 - -----
4800 930 2.70 981 2.88 1029 3.06 1075 3.23 1120 3.39 - - - - - -----
50009612.9910113.1810593.35--------------
3 HP and field supplied drive
ZR150 (12.5 ton) side duct
Air flow
(CFM)
Available external static pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2 in. filters. See the static resistance table for additional applications.
2. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP and field supplied drive Standard 3 HP and drive
3200 747 1.02 797 1.21 846 1.38 892 1.55 937 1.71 980 1.86 1023 2.02 1064 2.17 11042.3211442.48
3400 764 1.16 814 1.35 862 1.53 909 1.69 954 1.85 997 2.01 1039 2.16 1080 2.31 11212.4711602.62
3600 783 1.33 833 1.51 881 1.69 927 1.86 972 2.02 1016 2.17 1058 2.32 1099 2.48 11392.6311792.79
3800 803 1.51 853 1.69 901 1.87 948 2.04 992 2.20 1036 2.35 1078 2.50 1119 2.66 11592.8111992.97
4000 825 1.71 875 1.89 923 2.07 970 2.23 1014 2.39 1058 2.55 1100 2.70 1141 2.8611813.0112213.16
4200 849 1.92 899 2.11 947 2.29 993 2.45 1038 2.61 1082 2.77 1124 2.92 1165 3.0712053.2312453.38
4400 874 2.16 924 2.35 972 2.52 1019 2.69 1064 2.85 1107 3.01 1149 3.16 1190 3.3112313.4712703.62
4600 901 2.42 952 2.61 1000 2.78 1046 2.95 1091 3.11 1134 3.26 1177 3.42 1218 3.5712583.7212983.88
4800 930 2.70 981 2.88 1029 3.06 1075 3.23 1120 3.39 1163 3.54 1206 3.69 1247 3.8512874.0013274.16
5000 961 2.99 1011 3.18 1059 3.35 1106 3.52 1151 3.68 1194 3.84 1236 3.99 1277 4.14 1318 4.29 1357 4.45
5200 993 3.31 1043 3.49 1092 3.67 1138 3.84 1183 4.00 1226 4.15 1269 4.30 1310 4.46 1350 4.61 1390 4.77
5400 1027 3.64 1077 3.83 1126 4.00 1172 4.17 1217 4.33 1260 4.48 1302 4.64 13444.7913844.9414245.10
5600 1063 3.99 1113 4.18 1161 4.35 1207 4.52 1252 4.68 1296 4.84 1338 4.99 13795.1414195.2914595.45
5800 1100 4.36 1150 4.55 1198 4.72 1244 4.89 1289 5.05 1333 5.20 1375 5.36 14165.5114565.66 - -
6000 1138 4.75 1188 4.93 1237 5.11 1283 5.28 1328 5.44 1371 5.59 1413 5.74 - - - ---
620011785.1512285.3412775.5113235.68------------