5167531-YIM-J-1019
Johnson Controls Ducted Systems 23
120
(10)
208 16.0 110.0 24.9 3.0 9.6 5.5 0.0
None - - - 51.7 57.2 60 70
E18 13.5 2 37.5 58.8 65.7 60 70
E24 18.0 2 50.0 74.5 81.3 80 90
E36 25.5 2 70.8 100.5 107.4 110 110
E54 40.6 2 112.7 152.9 159.7 175 175
230 16.0 110.0 24.9 3.0 9.6 5.5 0.0
None - - - 51.7 57.2 60 70
E18 18.0 2 43.3 66.1 73.0 70 80
E24 24.0 2 57.7 84.2 91.0 90 100
E36 34.0 2 81.8 114.2 121.1 125 125
E54 54.0 2 129.9 141.9 148.8 175 175
460 7.8 52.0 12.1 1.6 4.7 2.2 0.0
None - - - 25.5 27.7 30 35
E18 18.0 2 21.7 32.9 35.7 35 40
E24 24.0 2 28.9 42.0 44.7 45 45
E36 34.0 2 40.9 57.0 59.7 60 60
E54 54.0 2 65.0 70.8 73.6 80 80
575 5.7 38.9 8.9 1.4 3.6 1.8 0.0
None - - - 19.1 20.9 20 25
E18 18.0 2 17.3 26.2 28.4 30 30
E24 24.0 2 23.1 33.4 35.6 35 40
E36 34.0 2 32.7 45.4 47.6 50 50
E54 54.0 2 52.0 56.5 58.7 70 70
150
(12.5)
208 22.4 149.0 35.0 2.1 14.0 5.5 0.0
None - - - 72.8 78.3 90 100
E18 13.5 2 37.5 72.8 78.3 90 100
E24 18.0 2 50.0 80.0 86.8 90 100
E36 25.5 2 70.8 106.0 112.9 110 125
E54 40.6 2 112.7 158.4 165.2 175 175
230 22.4 149.0 35.0 2.1 14.0 5.5 0.0
None - - - 72.8 78.3 90 100
E18 18.0 2 43.3 72.8 78.5 90 100
E24 24.0 2 57.7 89.7 96.5 90 100
E36 34.0 2 81.8 119.7 126.6 125 150
E54 54.0 2 129.9 147.4 154.3 175 175
460 10.6 75.0 16.5 1.3 6.6 2.2 0.0
None - - - 35.5 37.7 45 45
E18 18.0 2 21.7 35.5 38.1 45 45
E24 24.0 2 28.9 44.3 47.1 45 50
E36 34.0 2 40.9 59.4 62.1 60 70
E54 54.0 2 65.0 73.2 76.0 80 90
575 7.7 54.0 12.0 0.7 5.2 1.8 0.0
None - - - 25.2 27.0 30 30
E18 18.0 2 17.3 28.2 30.4 30 35
E24 24.0 2 23.1 35.4 37.6 40 40
E36 34.0 2 32.7 47.4 49.6 50 50
E54 54.0 2 52.0 58.5 60.7 70 70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZR078-150 high static motor - without powered convenience outlet (continued)
Size
(tons)
Volt
Compressors
(each)
OD fan
motors
(each)
Supply
blower
motor
Pwr exh
motor
Pwr
conv
outlet
Electric heat option
MCA
1
(amps)
MCA
1
with pwr
exh (amps)
Max fuse
2
/
breaker
3
size (amps)
Max fuse
2
/
breaker
3
size with
pwr exh
(amps)
RLA LRA MCC FLA FLA FLA FLA Model kW Stages Amps