Note 1: For thermocouples or RTD input, only 0 or 0.0 is selectable, and the internal
resolution is 0.1.
dIP only affect the display, and has no affect to the accuracy of measurement or
control.
Define scale low limit of input. It is also the low limit of transmitter output (CtrL=POP
or SOP) and light bar display.
Define scale high limit of input. It is also the high limit of retransmission output
(CtrL=POP or SOP) and light bar display.
Scb is used to shift input to compensate the error caused by transducer, input signal,
or auto cold junction compensation of thermocouple.
PV_after_compensation=PV_before_compensation + Scb
It is generally set to 0. The incorrect setting will cause measurement mistake.
oP1 select the control output type:
oP=oP1.A x 1 + oP1.B x 10
oP1.A shows the output type of OUTP. It should be compatible with the module
installed in OUTP sockets.
oP1. A= 0, if output modules such as SSR voltage output, relay contact discrete
output, thyristor cross zero trigger output, and TRIAC no-contact discrete output are