32
installed in OUTP.
oP1. A= 1, 010mA linear current output. Linear current output module should be
installed to main output.
oP1. A= 2, 020mA linear current output. Linear current output module should be
installed to main output.
oP1. A= 3, spare
oP1.A=4, 4~20mA linear current output. Linear current output module should be
installed to main output.
oP1. A= 57, No applicable i n A I -518.
oP1.A=8, single channel phase-shift output. K5 module should be installed.
In this mode, AUX can not work as refrigerating output.
oP1.B shows the AUX output type. It works only when parameter oPL<0.
oP1.B=0, time proportional output. Output modules such as SSR voltage
output, relay contact discrete output, thyristor cross zero trigger output, and TRIAC
no-contact discrete output can be installed in OUTP.
oP1.B=1, 010mA linear current output. Linear current output module should be
installed to main output.
oP1.B=2, 020mA linear current output. Linear current output module should be
installed to main output.