The installer MUST use two wrenches
One to hold the gas inlet on the gas water heater and one to tighten the ½” swivel to 15mm
copper solder – supplied.
This is the correct way to install the gas inlet, without breaking the pipes.
If using a ½” female to hose tail connection with an 8mm hose, the gas flow volume will be
inhibited and this will decrease the gas pressure.
This gas water heater operates on gas pressure 2.8 kPa ONLY. Do not increase pressure.
If Installed Inside, ensure that;
The installer abides by SANS 10087-1 specifications of cross ventilation.
NB - If installed outside, a flue must be fitted as this unit is fitted with a flue sensor.
NB – If installed inside, a flue must be flued to the outside of the building.
NB - By Law, it must cut out within 4 minutes if no flue is fitted.
NB - Bridging out of the flue sensor is not permitted.
NB – A valid COC Certificate must accompany any warranty claim.
Rev 0 – 11/2017