EasyManua.ls Logo

3M Ranger 247 - Model 247 Over-Temperature Testing; Testing Model 247 Alarm Points

3M Ranger 247
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English
15
247021E  English
Ranger Blood and Fluid Warming Systems
testing the oveR-temPeRatuRe alaRm Points (48°C [±2] and 50°C [±2])
e over-temperature alarm test causes the Ranger irrigation unit to go into an over-temperature
test mode by manually overriding the primary control system and engaging the heaters� e Ranger
irrigation system is very responsive to heater input; therefore the test procedures are technique
sensitive� Read instructions thoroughly before beginning these tests�
e rst alarm point at 48°C (±2) alerts user to the rise in temperature (see step 7)� At the
50°C (±2) secondary alarm set point, the unit cuts power to the heaters (see step 8)�
7 Loosen the over-temperature
screw on the bottom of the Ranger
irrigation unit (see Fig� 3)� Listen for a
slight click as the microswitch opens
Loosen ½ turn more. is unit is
now in over-temperature test mode,
and the temperature output of the
unit should begin to rise� When the
Ranger display reads 48°C, verify that
an audible alarm sounds, the alarm
light illuminates, and the display
alternately ashes “HI” and the plate
temperature�
8� Listen for the power relay to click at 50°C (±2) (you can feel the click when holding the lower
le corner of the unit as you face the front display)� e click signies the secondary alarm
trip point and signals that power to the heaters has been shut o� e over-temperature alarm
sounds, the alarm light illuminates, and the alphanumeric display alternately reads “HI” and the
plate temperature� Watch the thermocouple temperature monitor to determine the units peak
temperature output (less than 1 minute)� e temperature reading on the monitor should peak at
50°C (±2)�
note: If the temperature displayed on the thermocouple monitor exceeds 52°C during the test,
tighten the over-temperature test screw on the bottom of the Ranger irrigation unit, unplug it,
and run cold uids through the warming cassette� is returns the unit to normal operating
temperature� Call Arizant Healthcare Inc� Technical Support
9 e secondary alarm is designed to latch� Verify this feature by momentarily turning o the
power switch, then turning it on again� e Ranger irrigation unit should continue alarming
throughout this sequence�
10� Securely tighten the over-temperature screw, turn o the Ranger irrigation unit, and unplug the
unit� Once power is cut to the Ranger irrigation unit, the alarm will cease� e unit is ready to
return to service aer it cools to normal operating temperature (approximately 20-30 minutes)�
Fig. 3: Ranger irrigation over-temperature screw
Over-temperature
screw
Model 247

Other manuals for 3M Ranger 247

Related product manuals