SETUP
Page 37
5.6 SETUP 5: Alarm Water and Gas in oil
SETUP 5 is accessed by pressing the '→' arrow or <F1> in
SETUP 4.
Use <F2...F5> to access other submenus in which limits,
switching delays and hysteresis can be selected.
In the setup 5 the parameters of the limits water in Oil, gas
in oil, H2 in oil and CO in oil can be set.
Water in Oil content 5.6.1
Limit value
Defines the switch-on point for the alarm signal.
Setting range: 0...1000000 ppm
Switching delay
Defines the switch-on delay for the alarm signal.
Setting range: 0...900 s
Hysteresis
Defines the hysteresis for the switching point.
Setting range: 1...100000 ppm
Gas in Oil (Total gas in Oil) content 5.6.2
Limit value
Defines the switch-on point for the alarm signal.
Setting range: 0...1000000 ppm