Station communication
M15031-1 v9
Table 152. Communication protocols
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Protocol IEC 60870–5–103
Communication speed for the IEDs 9600 or 19200 Bd
Protocol DNP3.0
Communication speed for the IEDs 300–115200 Bd
Protocol TCP/IP, Ethernet
Communication speed for the IEDs 100 Mbit/s
Protocol LON
Communication speed for the IEDs 1.25 Mbit/s
Protocol SPA
Communication speed for the IEDs 300–38400 Bd
GUID-E8B5405C-241C-4DC2-8AB1-3FA77343A4DE v2
Table 153. IEC 61850-9-2 communication protocol
Function Value
Protocol IEC 61850-9-2
Communication speed for the IEDs 100BASE-FX
M11927-1 v2
Table 154. LON communication protocol
Function Value
Protocol LON
Communication speed 1.25 Mbit/s
M11901-1 v2
Table 155. SPA communication protocol
Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899
M11921-1 v4
Table 156. IEC 60870-5-103 communication protocol
Function Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd
Generator protection REG670
1MRK 502 074-BEN M
Hitachi Power Grids 121
© Copyright 2017 Hitachi Power Grids. All rights reserved