EasyManua.ls Logo

ABB 1MRK002826-AG - Page 154

ABB 1MRK002826-AG
163 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Binary input/output modules Ordering no #10 Notes and rules
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1BIM and 1 BOM required in slots P3 and P4.
Slot position (front/rear
view)
P3/X31
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
1)
1/2 Case with 1 TRM
3/4 Case with 2 TRM
2)
Only for B30/C30
1/1 Case with 2 TRM
3)
Compression terminals 1MRK002960-KA C
No board in slot X X X X X X X X X
Binary output module 24
output relays (BOM)
1MRK000614-AB A A A A A A A A A A
4)
BIM 16 inputs, RL24,
24-30VDC, 50mA
1MRK000508-DD B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
BIM 16 inputs, RL48,
48-60VDC, 50mA
1MRK000508-AD C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
BIM 16 inputs, RL110,
110-125VDC, 50mA
1MRK000508-BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
BIM 16 inputs, RL220,
220-250VDC, 50mA
1MRK000508-CD E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
BIM 16 inputs, RL220,
220-250VDC, 120mA
1MRK000508-CE E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
BIM 16 inputs, RL24,
24-30VDC, 50mA, enhanced
pulse counting
1MRK000508-HA F F F F F F F F F
BIM 16 inputs, RL48,
48-60VDC, 50mA, enhanced
pulse counting
1MRK000508-EA G G G G G G G G G
BIM 16 inputs, RL110,
110-125VDC, 50mA,
enhanced pulse counting
1MRK000508-FA H H H H H H H H H
BIM 16 inputs, RL220,
220-250VDC, 50mA,
enhanced pulse counting
1MRK000508-GA K K K K K K K K K
IOM 8 inputs, RL 24-30 VDC,
50mA, 10+2 output relays
1MRK000173-GD L1 L1 L1 L1 L1 L1 L1 L1 L1
IOM 8 inputs, RL 48-60 VDC,
50mA, 10+2 output relays
1MRK000173-AE M1 M1 M1 M1 M1 M1 M1 M1 M1
IOM 8 inputs, RL 110-125
VDC, 50mA, 10+2 output
relays
1MRK000173-BE N1 N1 N1 N1 N1 N1 N1 N1 N1
IOM 8 inputs, RL 220-250
VDC, 50mA, 10+2 output
relays
1MRK000173-CE P1 P1 P1 P1 P1 P1 P1 P1 P1
IOM 8 inputs, RL 220-250
VDC, 110mA, 10+2 output
relays
1MRK000173-CF P2 P2 P2 P2 P2 P2 P2 P2 P2
IOM with MOV 8 inputs, RL
24-30 VDC, 50mA, 10+2
output relays
1MRK000173-GC U U U U U U U U U
IOM with MOV 8 inputs, RL
48-60 VDC, 50mA, 10+2
output relays
1MRK000173-AD V V V V V V V V V
IOM with MOV 8 inputs, RL
110-125 VDC, 50mA, 10+2
output relays
1MRK000173-BD W W W W W W W W W
IOM with MOV 8 inputs, RL
220-250 VDC, 50mA, 10+2
output relays
1MRK000173-CD Y Y Y Y Y Y Y Y Y
mA input module MIM 6
channels
1MRK000284-AB R R R R R R R R R
5)
SOM static output module, 6
heavy duty static outputs,
250 VDC + 6 output relays
1MRK002614-CA T2 T2 T2 T2 T2 T2 T2 T2
6)
Selection for
position #10
C
Generator protection REG670
1MRK 502 074-BEN M
Version 2.2
154 Hitachi Power Grids
© Copyright 2017 Hitachi Power Grids. All rights reserved

Related product manuals