EasyManua.ls Logo

ABB 1MRK002826-AG - Binary inputs and outputs

ABB 1MRK002826-AG
163 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Binary inputs and outputs
IP15844-1 v1M12576-1 v13
Table 15. BIM - Binary input module
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V
48/60 V
110/125 V
220/250 V
RL ±20%
RL ±20%
RL ±20%
RL ±20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency 10 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
*Debounce filter Settable 1–20 ms
Binary input operate time
(Debounce filter set to 0 ms)
3 ms -
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
M50609-2 v10
Table 16. BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V
48/60 V
110/125 V
220/250 V
RL ±20%
RL ±20%
RL ±20%
RL ±20%
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
-
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
*Debounce filter Settable 1-20 ms
Binary input operate time
(Debounce filter set to 0 ms)
3 ms -
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
Generator protection REG670
1MRK 502 074-BEN M
Version 2.2
Hitachi Power Grids 57
© Copyright 2017 Hitachi Power Grids. All rights reserved