Table 45. High speed distance protection ZMFPDIS, ZMFCPDIS
Function Range or value Accuracy
Number of zones 5 selectable
directions, 2 fixed
directions
-
Minimum operate current, Ph-
Ph and Ph-E
(5-6000)% of IBase ±1.0% of I
r
Positive sequence reactance
reach, Ph-E and Ph-Ph loop
(0.01 - 3000.00)
ohm/p
Pseudo continuous ramp:
±2.0% of set value
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Angle: At 0 degrees and 85 degrees
IEC 60255-121 points A,B,C,D,E
Ramp of shots:
±2.0% of set value
Conditions:
IEC 60255-121 point B
Positive sequence resistance
reach, Ph-E and Ph-Ph loop
(0.00 - 1000.00)
ohm/p
Zero sequence reactance reach (0.01 - 9000.00)
ohm/p
Zero sequence resistive reach (0.00 - 3000.00)
ohm/p
Fault resistance reach, Ph-E
and Ph-Ph
(0.01 -9000.00)
ohm/l
Dynamic overreach < 5% at 85 degrees
measured with CVTs
and 0.5 < SIR < 30,
IEC 60255-121
-
Reset ratio 105% typically -
Directional blinders Forward: -15 – 120
degrees
Reverse: 165 – -60
degrees
Pseudo continuous ramp:
±2.0 degrees, IEC 60255-121
Resistance determining the
load impedance area - forward
(0.01 - 5000.00)
ohm/p
Pseudo continuous ramp:
±2.0% of set value
Conditions:
Tested at ArgLd = 30 degrees
Ramp of shots:
±5.0% of set value
Conditions:
Tested at ArgLd = 30 degrees
Angle determining the load
impedance area
5 - 70 degrees Pseudo continuous ramp:
±2.0 degrees
Conditions:
Tested at RLdFw = 20 ohm/p
Definite time delay to trip, Ph-E
and Ph-Ph operation
(0.000-60.000) s ±0.2% of set value or ±35 ms whichever is greater
Operate time 16 ms typically, IEC
60255-121
-
Reset time at 0.1 to 2 x Zreach Min. = 20 ms
Max. = 35 ms
-
GUID-88E02516-1BFE-4075-BEEB-027484814697 v2
Table 46. Pole slip protection PSPPPAM
Function Range or value Accuracy
Impedance reach (0.00 - 1000.00)% of Zbase ±2.0% of U
r
/I
r
Zone 1 and Zone 2 trip counters (1 - 20) -
Generator protection REG670
1MRK 502 074-BEN M
74 Hitachi Power Grids