EasyManua.ls Logo

ABB 1MRK002826-AG - Wide area measurement system

ABB 1MRK002826-AG
163 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wide area measurement system
GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v5
Table 52. Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) PMUREPORT
Influencing quantity Range Accuracy
Signal frequency ± 0.1 x f
r
≤ 1.0% TVE
Signal magnitude:
Voltage phasor
Current phasor
(0.1–1.2) x U
r
(0.5–2.0) x I
r
Phase angle ± 180°
Harmonic distortion 10% from 2nd – 50th
Interfering signal:
Magnitude
Minimum frequency
Maximum frequency
10% of fundamental signal
0.1 x f
r
1000 Hz
Generator protection REG670
1MRK 502 074-BEN M
Version 2.2
Hitachi Power Grids 77
© Copyright 2017 Hitachi Power Grids. All rights reserved