Wide area measurement system
GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v5
Table 52. Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) PMUREPORT
Influencing quantity Range Accuracy
Signal frequency ± 0.1 x f
r
≤ 1.0% TVE
Signal magnitude:
Voltage phasor
Current phasor
 
(0.1–1.2) x U
r
(0.5–2.0) x I
r
Phase angle ± 180°
Harmonic distortion 10% from 2nd – 50th
Interfering signal:
Magnitude
Minimum frequency
Maximum frequency
 
10% of fundamental signal
0.1 x f
r
1000 Hz
Generator protection REG670
1MRK 502 074-BEN M
 
Hitachi Power Grids 77