non-volatile fault storageDIP switch 1Configuration of
short-circuit detectionDIP switch 2
disabledDIP switch 3
Remote Test/ResetDIP switch 4
Output circuit
Relay, 1st c/o (SPDT) contact11-12/14Kind of output
Relay, 2nd c/o (SPDT) contact21-22/24
closed-circuit principleOperating principle
AgNi alloy, Cd freeContact material
24 V / 10 mAMinimum switching voltage / Minimum switching current
See the relay data sheet.Maximum switching voltage / Maximum switching
current
4 AAC-12 (resistive) at 230 VRated operational voltage
U
e
and rated operational
current I
e
3 AAC-15 (inductive) at 230 V
4 ADC-12 (resistive) at 24 V
2 ADC-13 (inductive) at 24 V
B 300Utilization category
(Control Circuit Rating
Code)
AC Rating (UL 508)
300 V ACMaximum rated operational
voltage
5 AMaximum continuous
thermal current at B 300
3600/360 VAMaximum making/breaking
apparent power at B 300
250 V AC - 4 AGeneral purpose rating
30 x 10
6
switching cyclesMechanical lifetime
0.1 x 10
6
switching cyclesElectrical lifetime at AC-12, 230 V AC, 4 A
10 A fast-actingN/C contactMaximum fuse rating to
achieve short-circuit
protection
10 A fast-actingN/O contact
General data
100%Duty cycle
85.6 × 22.5 × 103.7 mm (3.37 × 0.89 × 4.08 in)Dimensions (Height × Width × Depth)
0.141 kgScrew connection
technology
Weight, net
0.130 kgEasy Connect Technology
(push-in)
DIN rail (IEC/EN 60715), snap-on mounting without any
tool
Mounting
10 mm (0.39 in) if switching current > 2 AVerticalMinimum distance to other
units
10 mm (0.39 in) if switching current > 2 AHorizontal
UL 94 V-0Material of housing
IP50HousingDegree of protection
IP20Terminals