Loading...
± 40 μV on mV or thermocouple, 200 mohm on RTD,
0.2% on potentiometer or ± 0.05% of input value
Calibration and linearity
accuracy
Input
± 2 μV, 20 mohm, 0.02% or ± 0.01% of input value
for a 1 °C change.
Temperature influence
± 0.1% of full scaleCalibration accuracyAnalog Output
± 0.05% of full scaleLinearity error
± 0.05% of full scale for a min to max supply changeSupply voltage influence
± 0.05% of full scale for a 0…100% load resistance
change
Load influence
± 0.01% on zero and span for a 1 °C changeTemperature influence
Power supply indication (green)PWRSignalling LEDs
Burnout (red)BURN
Alarm A (red)A
Alarm B (red)B
Environmental conditions
Temperature limits -20 °C +60 °C (-4 °F +140 °F),
relative humidity max. 90% non condensing, up to 35 °C
(95 °F).
Operating
Temperature limits -45 °C +80 °C (-49 °F +176 °F)Storage
General
T35 DIN Rail according to EN 50022Mounting
114.5 × 22.5 × 99 mmDimensions (Height × Width × Depth)
approximately 160 gWeight
Screw terminal blocks, max. 2.5 mm
2
Terminal connection
IP20Protection class
Approvals
ATEX Ex II (1) G D
IECEx
TUV Certificate No. C-IS-236198-02, SIL 2 according to IEC 61511
DNV A-13778 and KR MIL20769-EL001 Certificates for maritime applications
For the complete list of approvals, see the relay data sheet.
Isolation data
1.5 kVIn/OutsIsolation voltage (Test
voltage)
1.5 kVIn/Supply
500 VAnalog Out/Supply
1.5 kVAnalog Out/Alarm Outs
1.5 kVAlarm Outs/Supply
1.5 kVAlarm Out/Alarm Out
For the complete relay technical data, see www.gminternational.com.
PR electronics 9116B1 universal converter
Ordering information
9116B1Universal converter - Uo 28 V DC (max. loop voltage)
4501Display / Programming front (not included in the ABB
delivery)
60 Technical data

Table of Contents