This input is not galvanic separated from measuring
input P1-P2
Remark
Output contacts
2 changeover contactsContacts
5 AThermal current I
th
3 A / AC 230 Vto AC 15Switching capacity
(IEC/EN 60947-5-1)
2 A / DC 24 Vto DC 13
1.5 × 10
6
switching cyclesElectrical life at 4 A, 230 V AC, cos phi = 0.6
max. fuse rating: 6 A gG / gLNC contactShort-circuit strength
(IEC/EN 60947-5-1)
max. fuse rating: 10 A gG / gLNO contact
≥ 30 × 10
6
switching cyclesMechanical life
Terminals
1 × 0.5 … 2.5 mm
2
(2 × 20 … 14 AWG)Stranded ferruledWire size
2 × 0.5 … 1.5 mm
2
(2 × 20 … 16 AWG)
1 × 0.5 … 4 mm
2
(1 × 20 … 12 AWG)Solid
2 × 0.5 … 2.5 mm
2
(2 × 20 … 14 AWG)
Max. 0.8 Nm (7 lbf·in)Tightening torque
Indicators
on, when auxiliary supply connectedGreen LED
on, when overtemperature or broken wire, short circuit
is detected
Red LED
General data
Continuous operationOperating mode
-20 °C … +60 °C (-4 °F … +140 °F)OperationTemperature range
-20 °C … +60 °C (-4 °F … +140 °F)Storage
< 2000 mAltitude
Limit value class BInterference suppressionsEMC (EN 55011)
IP40HousingDegree of protection
(IEC/EN 60529)
IP20Terminals
Thermoplastic with V0-behavior according to UL subject
94
Housing
20 / 060 / 04Climate resistance (IEC/EN 60068-1)
Amplitude 0.2 mm, frequency 10 … 55 HzVibration resistance (IEC/EN 60068-2-6)
DIN railMounting (IEC/EN 60715)
160 gWeight
22.5 × 90 × 102 mmDimensions
Approvals
ATEX Ex II (2) G D
Isolation data
Note: The supply and measurement circuits are not electrically isolated. Use a dedicated power supply for the
PTC relay(s).
4 kVRated impulse withstand voltage between all isolated
circuits
2Pollution degree
58 Technical data