Aim
MIPIP
IB
6.2
.
1.7
D
Page
7
ASEA
BROWN
BOVERI
rated
asymmetrical
short
circuit
current
,
the
circuit
breaker
be
inspected
regardless
of
any
time
period
or
number
of
operations
.
Also
,
when
the
circuit
breaker
is
applied
on
reclosing
duty
,
it
should
be
inspected
immediately
afterthe
series
of
fault
operations
in
the
same
range
of
currents
.
The
condition
of
the
circuit
breaker
after
interruption
de
-
pends
on
circuit
conditions
regarding
such
things
as
power
factor
,
X
/
R
ratio
and
relay
delay
times
.
Experience
with
specific
circuits
will
indicate
the
future
amount
of
mainte
-
nance
that
will
be
required
for
the
various
breakers
and
then
procedural
modification
can
follow
.
Where
unusual
service
conditions
exist
,
as
covered
by
ANSI
Standard
C
37.04
,
it
must
be
assumed
that
these
conditions
were
considered
at
the
time
of
order
;
that
the
equipment
supplied
was
designed
for
the
special
applica
-
tion
;
and
that
an
appropriate
supplemental
maintenance
program
has
been
developed
.
These
maintenance
instruc
-
tions
cover
only
circuit
breakers
used
under
standard
usual
service
conditions
.
After
normal
service
without
major
fault
interruption
,
the
following
tests
and
adjustments
should
be
made
.
NOTE
:
The
following
tabulated
tests
and
adjustments
are
all
that
are
normally
necessary
for
proper
maintenance
and
operation
of
the
HK
circuit
breaker
.
The
remaining
portions
of
the
breaker
-
close
coil
assembly
,
shunt
trip
device
,
control
relay
,
auxiliary
switch
and
motor
require
no
main
-
tenance
during
the
standard
life
of
the
circuit
breaker
regardless
of
the
operatinq
duty
.
5.2
CONTACT
PRESSURE
(
See
Figure
4
)
(
A
)
With
the
circuit
breaker
withdrawn
from
the
switch
-
board
,
the
following
step
-
by
-
step
procedure
should
be
followed
for
properly
checking
and
/
or
adjusting
the
contact
pressure
on
an
HK
type
circuit
breaker
.
1
.
Remove
interphase
barrier
assembly
and
remove
arc
chutes
as
described
previously
.
2
Turn
racking
screw
clockwise
approximately
two
to
three
turns
until
the
racking
-
unlocking
lever
snaps
into
the
first
position
corresponding
to
the
DISCONNECT
position
.
3
.
Manually
slow
-
close
the
circuit
breaker
as
described
in
parag
raph
3.7
,
but
only
to
the
point
that
the
arc
contacts
just
touch
.
All
arcing
contacts
shouldtouch
within
1
/
32
"
,
after
all
free
play
has
been
removed
by
pulling
the
bridge
arm
toward
the
open
position
.
4
.
Continue
the
slow
-
close
operation
to
fully
close
the
breaker
.
Each
pole
should
have
approximately
7
/
64
to
3
/
16
main
contact
compression
measured
at
"
A
between
the
edge
of
the
metal
stop
plate
and
the
main
contact
stop
.
(
This
dimension
measured
on
either
side
is
sufficient
)
.
A
rod
or
drill
of
these
sizes
can
be
used
for
measuring
.
Complete
charging
the
sprinqs
and
remove
the
slow
close
bracket
.
Fig
.
4
Contact
Pressure
and
Bridge
Pivot
Pressure
5
.
Open
the
breaker
.
Fast
close
the
breaker
.
Each
pole
should
have
between
7
/
64
"
to
3
/
16
"
main
contact
pressure
.
At
this
point
,
if
the
adjustments
are
correct
,
complete
steps
B
6
,
B
7
,
B
8
and
B
9
following
.
(
B
)
If
any
adjustment
is
incorrect
,
use
the
following
proce
-
dure
to
readjust
contact
pressure
or
to
initially
adjust
when
changes
are
made
.
1
Completely
slow
-
close
the
circuit
breaker
and
set
each
pole
for
7
/
64
"
main
contact
compression
at
"
A
(
A
7
/
64
rod
ordrill
should
fit
tightly
between
the
EDGE
of
the
metal
stop
plate
and
the
main
contact
stop
.
)
2
.
Open
the circuit
breaker
,
manually
recharge
the
closing
springs
,
and
partially
slow
-
close
the
circuit
breaker
until
the
arcing
contacts
of
any
pole
or
poles
just
touch
.
3
.
Advance
the
adjustment
of
the
lagging
pole
or
poles
so
that
the
three
arcing
contacts
touch
simultaneously
within
1
/
32
"
.
This
adjustment
is
made
by
loosening
locking
bolt
or
set
screw
(
depending
on
model
) (
2
)
and
rotating
adjusting
stud
(
3
)
.
4
Complete
slow
-
close
operation
to
fully
closed
position
and
check
that
the
main
contact
compression
of
the
pole
or
poles
that
were
advanced
does
not
exceed
3
/
16
"
.
Also
,
the
arcing
contact
springs
on
these
poles
should
not
be
fully
compressed
.
If
the
3
/
16
"
dimension
is
exceeded
,
the
entire
procedure
should
be
repeated
to
obtain
the
correct
gap
at
A
.
NOTE
:
Occasionally
,
the
centerpole
contact
pressure
may
slightly
exceed
3
/
16
"
However
,
if
the
outer
poles
are
within
3
/
16
"
dimension
and
the
arcing
contact
springs
of
the
Courtesy of NationalSwitchgear.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 5HK Series and is the answer not in the manual?

ABB 5HK Series Specifications

General IconGeneral
BrandABB
Model5HK Series
CategoryCircuit breakers
LanguageEnglish

Related product manuals