Below is Roles-to-rights Mapping information for Edge Gateway web server users:
11.3 Ports and services
The ABB Ability
TM
Edge Industrial Gateway provides 2x 10/100 Mbps Ethernet ports:
ETH 0.
ETH 1 (Local LAN).
The Internet Protocol (IP) communications in ABB Ability
TM
Edge Industrial Gateway rely on two
parameters: IP Address and Ports. An Ethernet port (Local LAN) in ABB Ability
TM
Edge Industrial
Gateway represents a physical end point to the network (LAN/WAN), to which it is connected. Typically
during commissioning, a network administrator assigns an IP address to each of the ETHs associated
with ABB Ability
TM
Edge Industrial Gateway.
By default, the ETH 1 (Local LAN) is assigned an IP address of 192.168.2.1. During commissioning we
recommend changing these IP addresses. For local view models, ETH 0 can be connected to internet for
firmware updates. The Cloud-connected version uses continuously ETH 0 for data connection into ABB
Cloud.
11.3.1 Ports
Ports are used in IP communications along with IP address. Ports represent a logical end point through
which data flows from a source to the destination machine. Ports are identified by numbers ranging
from 0 to 65535.
Software processes within ABB Ability
TM
Edge Industrial Gateway communicate on the network through
a combination of IP Address, Port and a communication protocol. A communication protocol, such as
HTTP, Modbus TCP, signifies a set of rules to be used when sending/receiving data over the network.
The table below list the ports used by various software processes in ABB Ability
TM
Edge Industrial
Gateway accomplishing a specific functionality.
Please note that WiFI & Cellular is available only for certain models.
CRUD - Create Read Update Delete
CRU - Create Read Update
RU - Read Update
R - Read
Applicable
to Edge
Owner Manager Energy
responsible
Maintenance
responsible
Staff Guset
as owner,
except for
EULA
as staff + some
settings for
energy
as staff + some
settings for
asset
only
dashboard
 yes RU R R R R
Site groups yes CRUD CRUD R R R
Site Settings: energy billing, cost plan yes CRUD CRUD CRUD R R
Site Settings: User mgmt + assign
roles yes CRUD RUD
Site user logs (activities on UI) yes R R
Asset (flat list) view (from
commissioning), navigation yes R R R R R
Application Type Application
Name
Interface Port Number Default state Connection Type
Web Server (Local view)
HTTPS   Open/Inbound TCP
Daemon Server
(Provision Tool)
HTTPS   Open/Inbound TCP
DHCP (Dynamic IP) DHCP   Open/Inbound UDP
DHCP (Dynamic IP) DHCP   Open/Inbound UDP
Time Sync NTP   Closed/Outbound UDP
DNS (Name resolution) DNS   Closed/Outbound TCP
Modbus TCP (Device
configuration)
Modbus TCP   Open/Inbound TCP
Modbus TCP (Field
devices communication)
Modbus TCP   Closed/Outbound TCP
FOTA HTTPS   Closed/Outbound TCP