Chapter 2 – Overview of the ACS 502/504
ACS 502 Installation & Start-up Manual 2-23
Table 2-6 Heater Sizes for Square D Relays
Heater Code Amps
AR .45 28.0 – 30.0
AR .49 31.0 – 33.0
AR .54 34.0 – 36.0
AR .59 37.0 – 39.0
AR .65 40.0 – 42.0
AR .71 43.0 – 46.0
AR .78 47.0 – 50.0
AR .86 51.0 – 52.0
AR .95 53.0 – 56.0
AR 1.05 57.0 – 60.0
AR 1.15 61.0 – 66.0
AR 1.26 67.0 – 73.0
AR 1.39 74.0 – 81.0
AR 1.53 82.0 – 90.0
AR 1.68 91.0 – 105.0
AR 1.85 106.0 – 115.0
AR 2.04 116.0 – 125.0
AR 2.24 126.0 – 135.0
AR 2.46 136.0 – 147.0
AR 2.71 148.0 – 158.0
AR 2.98 159.0 – 174.0
AR 3.28 175.0 – 194.0
AR 3.62 195.0 – 220.0
AR 3.98 221.0 – 247.0
AR 4.37 248.0 – 276.0
AR 4.80 277.0 – 307.0
AR 5.3 308.0 – 345.0
AR 5.8 346.0 – 381.0
AR 6.4 382.0 – 420.0
AR 7.0 421.0 – 465.0