Appendix A – ACS/ACC/ACP 604/607 Technical Data
ACS/ACC/ACP 604/607 Drives ACx=ACS/ACC/ACP A-5
Efficiency and
Cooling
Efficiency: Approximately 98% at nominal power level
Cooling Method: Internal fan, flow direction from the bottom to the top
Ambient Conditions
Environmental limits of the ACS/ACS/ACP 600 drives are given below.
The drives are to be used in a heated, indoor, controlled environment.
1)
At sites over 1000 m (3300 ft.) above sea level, the maximum output current is
derated 1% for every additional 100 m (330 ft.). If the installation site is higher than
2000 m (6600 ft.) above sea level, please contact your local ABB distributor or office for
further information.
2)
See subsection
Output Current Temperature Derating
on page A-3.
Fuses
Input fuse ratings of the ACS/ACC/ACP 607 and recommended input
fuse ratings of the ACS/ACC/ACP 604 are below.
A minimum rated
current in amperes,
A
2
s maximum I
2
t value, V rated voltage in volts.
Only ultra rapid fuses guarantee proper protection for the rectifier
semiconductors.
ACS/ACC/ACP 600 Operation
installed for stationary use
Storage
in the protective package
Transportation
in the protective package
Installation Site
Altitude
Nominal output power at
0 to 1000 m (3300 ft) above
sea level
1)
--
Air Temperature 0 to +40 °C (32 to 104°F)
2)
(IP 21/22 and ACx 607, IP 54)
0 to +25 °C (32 to 77°F)
2)
(ACx 601, IP 54)
-40 to +70 °C (-40 to +158°F) -40 to +70 °C (-40 to +158°F)
Relative Humidity 5 to 95% Max. 95% Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination
Levels
(IEC 721-3-3)
No conductive dust allowed.
Boards without coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 3C3
Solid particles: Class 3S2
Boards without coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards without coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Atmospheric
Pressure
70 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Vibration
(IEC 68-2-6)
Max. 0.3 mm (0.01 in.)
(2 to 9 Hz),
max. 1 m/s
2
(3.3 ft./s
2
)
(9 to 200 Hz) sinusoidal
Max. 1.5 mm (0.06 in.)
(2 to 9 Hz),
max. 5 m/s
2
(16.4 ft./s
2
)
(9 to 200 Hz) sinusoidal
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
max. 15 m/s
2
(49 ft./s
2
)
(9 to 200 Hz) sinusoidal
Shock
(IEC 68-2-29)
Not allowed Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Free Fall Not allowed 250 mm (10 in.) for weight
under 100 kg (220 lbs.)
100 mm (4 in.) for weight over
100 kg (220 lbs.)
250 mm (10 in.) for weight
under 100 kg (220 lbs.)
100 mm (4 in.) for weight over
100 kg (220 lbs.)

Table of Contents