129 ACS2000 AFE 2MVA UM 3BHS355653 ZAB E01 REV. H
8.5.2 Start sequence of the drive
Not ready on
Ready on
Ready run
Ready ref
On command
AFE Ready on
DC link charges
MCB closes
INU starts to modulate
Start command
Operation
AFE Ready ref
Ready on conditions:
Auxiliary supply on
AFE - INU door
closed and locked
Drive not grounded
No emergency off
No fault
&
Charging
Fan switches on