R6…R9 Quick installation guide 11
R6-
R9
R6…R9 Ratings and fuses
I
II
ACS580
-o1
Input
rating
Output ratings Maximum
losses
Frame
size
Nominal use Heavy duty use
I
1N
I
2Ld
P
Ld
I
2Hd
P
Hd
A A kW A kW W
3-phase U
N
= 480 V (440…480 V)
124A-4 124 124 100 96 75 1476 R6
156A-4 156 156 125 124 100 1976 R7
180A-4 180 180 150 156 125 2346 R7
240A-4 240 240 200 180 150 3336 R8
260A-4 260 260 200 240* 150 3936 R8
361A-4 361 361 300 302 250 4836 R9
414A-4 414 414 350 361** 300 6036 R9
* 130% overload only
** 125% overload only
ACS580
-01-
UL
I
N
Voltage rating Bussmann
type
1)
UL class
A V
3-phase U
N
= 480 V (440…480 V)
124A-4 200 600 JJS-200 T
156A-4 225 600 JJS-225 T
180A-4 300 600 JJS-300 T
240A-4 350 600 JJS-350 T
260A-4 400 600 JJS-400 T
361A-4 500 600 JJS-500 T
414A-4 600 600 JJS-600 T
1) ABB does not require Bussmann brand fuses. Fuses which meet
the appropriate UL class type, current rating, and are rated at 600V,
200 kA may be used.
3AXD50000009286 Rev D