44 R6…R9 Quick installation guide
For information on reforming the capacitors, see Converter module capacitor reforming
instructions (3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents
.
Select the power cables
Size the power cables according to local regulations to carry the nominal current given
on the type designation label of your drive.
Ensure the cooling
See table I on page 11 for the losses. The allowed operating temperature range of the
drive is -15 to +50 °C (+5 to +122 °F). No condensation or frost is allowed. For more
information on the ambient temperature and derating, see chapter Technical data in
ACS580-01 (0.75 to 250 kW) hardware manual (3AXD50000018826 [English]).
Protect the drive and input power cable
See table II on page 11 for the fuses.
If you use gG fuses, make sure that the operating time of the fuse is below 0.5 seconds.
Follow the local regulations.
Install the drive on the wall
Warning! The drive module is heavy (42 to 103 kg / 93 to 227 lb). Use a suitable
lifting device. Do not lift the module manually. Make sure that the wall and the
fixing devices can carry the weight.
See figure R6…R9 Figures A on page 75.