7
R1…R4 Ratings and fuses
I
Type
ACS580-
01
Input
rating
Output ratings Maximum
heat
dissipation
Frame
size
Nominal use Heavy duty use
I1N I
Ld
P
Ld
I
Hd
P
Hd
A A hp A hp W
3-phase U
N
= 480 V (440…480 V)
02A1-4 2.1 2.1 1 1.6 0.75 45 R1
03A0-4 3 3 1.5 2.1 1 55 R1
03A5-4 3.5 3.5 2 3 1.5 66 R1
04A8-4 4.8 4.8 3 3.4 2 84 R1
06A0-4 6 6 3 4 3 106 R1
07A6-4 7.6 7.6 5 4.8 3 133 R1
012A-4 12 12 7.5 7.6 5 174 R1
014A-4 14 14 10 11 7.5 228 R2
023A-4 23 23 15 14 10 322 R2
027A-4 27 27 20 21 15 430 R3
034A-4 34 34 25 27 20 525 R3
044A-4 44 44 30 34 25 619 R3
052A-4 52 52 40 40 30 835 R4
065A-4 65 65 50 52 40 1024 R4