9
R5 Ratings and fuses
I
II
NEC
type
ACS580
-01-
Input
rating
Output ratings Maximum
heat
dissipation
Frame
size
Nominal use Heavy duty use
I
1N
I
Ld
P
Ld
I
Hd
P
Hd
A A hp A hp
W
3-phase U
N
= 480 V (440…480 V)
077A-4 77 77 60 65 50 1240 R5
096A-4 96 96 75 77 60 1510 R5
IEC
type
ACS580
UL
I
N
Voltage rating Bussmann type
1)
UL class
A V
3-phase U
N
= 480 V (440…480 V)
077A-4 100 600 JJS-100 T
096A-4 150 600 JJS-150 T
1) ABB does not require Bussmann brand fuses. Fuses which meet
the appropriate UL class type, current rating, and are rated at 600V,
200 kA may be used.