10 EN – Quick installation and start-up guide
EN
DE
ES
FI
FR
IT
NL
RU
SV
TR
ZH
xx
xx
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
Ensure the cooling
See table I on page 5 (UL: table II on page 5) for the losses. The allowed operating
temperature range of the drive without derating is -15 to +50 °C (+5 to +122 °F). No
condensation or frost is allowed. For restrictions below 0 °C (+32 °F) and above +40
°C (+104 °F), see chapter Technical data in ACS580-01 user’s manual
(3AUA0000076333 [English]).
Protect the drive and input power cable
See tables III (on page 6) and IV (on page 6); (UL: table V on page 7) for the fuses.
If you are going to use gG fuses, check on the fuse time-current curve to ensure the
operating time of the fuse is below 0.5 seconds. Follow the local regulations.
Install the drive on the wall
See figure A on page 3.
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
from the drive. Measure the insulation resistance between each phase conductor and
the Protective Earth conductor using a measuring voltage of 1000 V DC. The
insulation resistance of an ABB motor must exceed 100 Mohm (reference value at
25 °C or 77 °F). For the insulation resistance of other motors, see the manufacturers
instructions.
Note: Moisture inside the motor casing will reduce the insulation resistance. If
moisture is suspected, dry the motor and repeat the measurement.