EasyManua.ls Logo

ABB ACS580-01 - Install Optional Modules, if any; Check the Compatibility with IT (Ungrounded) and Corner Grounded TN Systems; Reinstall Cover; Start-Up

ABB ACS580-01
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 EN – Quick installation and start-up guide
EN
DE
ES
FI
FR
IT
NL
RU
SV
TR
ZH
xx
xx
Install optional modules, if any
See chapter Electrical installation in ACS580-01 user’s manual (3AUA0000076333
[English]).
Check the compatibility with IT (ungrounded) and corner-
grounded TN systems
WARNING! Do not install the drive with the internal EMC filter connected on an
IT system (an ungrounded power system or a high-resistance-grounded [over
30 ohms] power system) or on a corner-grounded TN system.
If you connect the drive to an IT (ungrounded) system or a corner-grounded TN
system, disconnect the EMC filter before connecting the drive to the supply network.
For information on how to do it, see chapter Electrical installation in ACS580-01
user’s manual (3AUA0000076333 [English]).
Reinstall cover
See figure I on page 4.
1. Put the tabs on the inside of the cover top in their counterparts on the housing (a)
and then press the cover at the bottom (b).
2. Tighten the retaining screw with a screwdriver.
Start-up
This chapter describes the start-up of the drive using the First start assistant on the
assistant control panel.
Complete documentation of the drive firmware: program features, parameters and
fault tracing can be found in ACS580-01 user’s manual (3AUA0000076333 [English]).
For more information on using the assistant panels, see ACS-AP-x assistant control
panels user’s manual (3AUA0000085685 [English]).
Before you start
Ensure that the drive has been installed as described in chapter Installation on page
9.